Emerson ITR Manuel D’Utilisation

Page de 74
System Data
35
Table 13
Liebert Challenger ITR glycol cooled data, 50 Hz (continued)
System Type
Glycol Cooled
GLYCOOL
Self-Contained
Split Systems
Self-Contained
Indoor Unit
BR 070WG
BR 059E
BM 058G
Infrared Humidifier - Standard
Capacity, kg/hr (lb/hr)
5 (11)
5 (11)
5 (11)
kW
4.8
4.8
4.8
Steam Generating Humidifier - Optional
Capacity, kg/hr (lb/hr)
5 (11)
5 (11)
5 (11)
kW
3.9
3.9
3.9
Filter Section - Efficiencies per ASHRAE 52.1 - Disposable Type
20% efficiencies available in 51mm (2") - Standard, or optional 102mm (4") depths; other optional 102mm (4") efficiencies 
are: 30%, 40-45%, 60-65%
Nominal Size, mm (in)
724 x 749
(28.5 x 29.5)
724 x 749
(28.5 x 29.5)
724 x 749
(28.5 x 29.5)
Effective Surface Area, m
2
 (ft
2
)
2.2 (24.1)
2.2 (24.1)
2.2 (24.1)
Glycol Regulating Valve
Size,  in
1
1
1
Econ-O-Valve
Size, in
-
-
1
Cv
-
-
13.9
System Data*
MC_68WG
 
Flow Rate, l/s (GPM)
1.1 (17.5)
1.3 (20)
1.1 (17.5)
Unit Volume, liters (gallons)
7.5 (2.0)
7.5 (2.0)
15.0 (4.0)
Pressure Drop, kPa (ft.)
56.4 (18.9)
111.9 (37.5)
152.5 (51.1)
Connection Sizes Challenger ITR Unit
Condenser Supply
1-1/8 OD Cu
1-1/8 OD Cu
Condenser Return
1-1/8 OD Cu
1-1/8 OD Cu
Liquid Line
1/2 OD Cu
Suction Line
1-1/8 CD Cu
Humidifier Supply Line
1/4 OD Cu
1/4 OD Cu
1/4 OD Cu
Condensate Drain Line
1/2 FPT
1/2 FPT
1/2 FPT
Connection Sizes Condensing Unit
Condenser Supply
1-1/8 OD Cu
Condenser Return
1-1/8 OD Cu
Liquid Line
1/2 OD Cu
Suction Line
1-1/8 CD Cu
Drycooler 35°C (95°F) Ambient*
Model Number
DSF112-3PH
DSF174-3PH
DSF112-3PH
Drycooler Connections
2
2
2
Volume, liters (gallons)
5.8 (22.0)
6.9 (26.2)
5.8 (22.0)
Pressure Drop, kPa (ft.)
7.2 (2.4)
9.2 (3.1)
7.2 (2.4)
Fan, kW (hp)
.56 (3/4)
.56 (3/4)
.56 (3/4)
Glycol Pump - 3-Phase kW (hp)
1.1 (1.5)
1.1 (1.5)
1.1 (1.5)
Head, kPa (ft.)
262.6 (88.0)
262.6 (88.0)
262.6 (88.0)
Pump Suction and Discharge NPT, female
1-1/4 & 3/4
1-1/4 & 3/4
1-1/4 & 3/4
 * All data above is based on 40% ethylene glycol solution.