Emerson ITR Manuel D’Utilisation

Page de 74
Dimensional Drawings
41
Figure 15 Cabinet and floor planning dimensional data—Split System—Propeller fan condensing unit
A
B
C
Fan Rotation
CCW
(left side)
SL-11081
Pg 4
Left Air
Intake
Shaded area indicates
a minimum clearance of
18" (457mm) for proper air flow
Removable (front) panel for
access to high voltage and low voltage
connections and to refrigeration components
Shaded area indicates
a recommended clearance of
24" (610mm) for for component
access and removal
Shaded area indicates
a minimum clearance of
18" (457mm) for proper air flow
Right Air
Discharge
Removable (Right ) panel
for access to refrigeration component
C
C
C
C
C
Outdoor Propeller Fan Condensing Unit
Model
Width (A)
Depth (C)
Height (B)
Net Weight
lbs (kg)
60 Hz
50 Hz
Dimensions - Inches (mm)
PFH067A-_L
PFH066A-_L
53 (1343)
18 (457)
36-1/4 (918)
351 (159)