Electrical Data
43
15.0 E
LECTRICAL
 D
ATA
Table 16
Liebert Challenger ITR electrical data
1
—60 Hz
Model Type
Self-Contained
Split System Evaporator or Chilled Water
BR067A, BR071WG, BM061G
BR060E, BR102C
Voltage
All Voltages Are 3 Phase Unless Noted Otherwise
208
230
460
575
208
230
460
575
With Electric Reheat and Humidifier (Infrared or Steam Generating) (Note: See Table 17 for units w/SCR reheats.
2
)
Motor
1.5 hp (1.1 kW)
1.5 hp (1.1 kW)
FLA
68.0
65.0
32.3
24.6
60.6
55.4
28.1
24.6
WSA
83.6
80.0
39.7
30.8
75.8
69.3
35.1
30.8
OPD
90
90
40
30
80
70
40
35
Motor
2.0 hp (1.5 kW)
2.0 hp (1.5 kW)
FLA
69.8
66.6
33.1
25.2
62.4
57.0
28.9
25.2
WSA
85.4
81.6
40.5
31.5
78.0
71.3
36.1
31.5
OPD
90
90
45
30
80
80
40
35
Motor
3.0 hp (2.2 kW)
3.0 hp (2.2 kW)
FLA
72.9
69.4
34.5
26.4
65.5
59.8
30.3
26.4
WSA
88.5
84.4
41.9
33.0
81.9
74.8
37.9
33.0
OPD
90
90
45
35
90
80
40
35
Humidifier Only (Infrared or Steam Generating)
Motor
1.5 hp (1.1 kW)
1.5 hp (1.1 kW)
FLA
39.7
37.0
18.4
16.9
19.0
16.3
8.4
9.5
WSA
44.9
42.2
20.9
18.8
23.8
20.4
10.5
11.9
OPD
60
60
30
25
25
20
15
15
Motor
2.0 hp (1.5 kW)
2.0 hp (1.5 kW)
FLA
41.5
38.6
19.2
17.5
20.8
17.9
9.2
10.1
WSA
46.7
43.8
21.7
19.4
26.0
22.4
11.5
12.6
OPD
60
60
30
25
30
25
15
15
Motor
3.0 hp (2.2 kW)
3.0 hp (2.2 kW)
FLA
44.6
41.4
20.6
18.7
23.9
20.7
10.6
11.3
WSA
49.8
46.6
23.1
20.6
29.9
25.9
13.3
14.1
OPD
70
60
30
25
35
30
15
15
Electric Reheat Only (Note: See Table 17 for Self-contained units w/SCR reheats.
2
)
Motor
1.5 hp (1.1 kW)
1.5 hp (1.1 kW)
FLA
68.0
65.0
32.3
24.6
47.3
44.3
22.3
17.2
WSA
83.6
80.0
39.7
30.2
59.1
55.4
27.9
21.5
OPD
90
90
40
30
60
60
30
25
Motor
2.0 hp (1.5 kW)
2.0 hp (1.5 kW)
FLA
69.8
66.6
33.1
25.2
49.1
45.9
23.1
17.8
WSA
85.4
81.6
40.5
30.8
61.4
57.4
28.9
22.3
OPD
90
90
45
30
70
60
30
25
Motor
3.0 hp (2.2 kW)
3.0 hp (2.2 kW)
FLA
72.9
69.4
34.5
26.4
52.2
48.7
24.5
19.0
WSA
88.5
84.4
41.9
32.0
65.3
60.9
30.6
23.8
OPD
90
90
45
35
60
70
35
20
Without Electric Reheat and Humidifier
Motor
1.5 hp (1.1 kW)
1.5 hp (1.1 kW)
FLA
26.4
25.9
12.6
9.5
5.7
5.2
2.6
2.1
WSA
31.6
31.1
15.1
11.4
7.1
6.5
3.3
2.6
OPD
50
50
25
15
15
15
15
15
Motor
2.0 hp (1.5 kW)
2.0 hp (1.5 kW)
FLA
28.2
27.5
13.4
10.1
7.5
6.8
3.4
2.7
WSA
33.4
32.7
15.9
12.0
9.4
8.5
4.3
3.4
OPD
50
50
25
15
15
15
15
15
Motor
3.0 hp (2.2 kW)
3.0 hp (2.2 kW)
FLA
31.3
30.3
14.8
11.3
10.6
9.6
4.8
3.9
WSA
36.5
35.5
17.3
13.2
13.3
12.0
6.0
4.9
OPD
50
50
25
20
20
20
15
15
1.
Contact factory for 380-3-60 data.
2.
For Split System Evaporators with SCR reheat, use the values above.
The values above were calculated per UL Standard 1995.
FLA = Full Load Amps (Input Amps); WSA = Wire Size Amps (Minimum Supply Circuit Ampacity); OPD = Maximum Overcurrent Protective Device Size
RLA = Rated Load Amps; LRA = Locked Rotor Amps
* R = In the Row; M = In the Row with Econ-O-Coil