Emerson IS-WEB485ADPT Manuel D’Utilisation

Page de 60
Factory Settings
35
7.2
Liebert DS - Local Node Settings for Multiple Cards
If you use two cards of the same type with the Liebert DS, you will need to change the local node set-
ting of one card. These steps apply only when both cards are the same type, either:
• Two Liebert IntelliSlot Web cards (P/N IS-WEBLBDS)
or
• Two Liebert IntelliSlot 485 cards (P/N IS-485LBDS)
Terminal Emulation (Serial or TCP/IP Connection) / Telnet
To access local node settings:
1. Choose Factory Settings from the Main Menu.
2. Choose Advanced Communication Settings from the Factory 
Settings Menu.
3. Choose Local Node Settings from the Advanced 
Communication Settings Menu.
4. Choose Node 1 from the Local Node Settings Menu, then use the 
following guide to make changes.
If there are two Liebert IntelliSlot Web cards or two Liebert 
IntelliSlot 485 cards, you must change the address of one card 
• For the Liebert IntelliSlot Web card, the default address is 1
For two Web cards, set the address of the second card to 2.
• For the Liebert IntelliSlot 485 card, the default address is 2
For two 485 cards, set the address of the second card to 1.
Table 22
Factory default MAC addresses
Liebert IntelliSlot Card
Part Number
Factory Default
MAC Address
Set Node 1 Address
of Second Card to:
Liebert IntelliSlot Web Card-LBDS
IS-WEBLBDS
0x01
2
Liebert IntelliSlot 485 Card-LBDS
IS-485LBDS
0x02
1
Liebert DS
Factory Settings Menu
----------------------
1: Advanced Communication 
Settings
2: Reset to Factory Defaults
<ESC>: Cancel menu level
Please select a key ?>
Liebert DS
Advanced Communication Settings
Menu
--------------------------------
1: Local Node Settings
2: Managed Device Settings
2: Reset to Default
<ESC>: Cancel menu level
Please select a key ?>
Liebert DS
Local Node Settings Menu
-------------------------
1: Node ID: 1
2: Communication Rate: 38400
3: Maximum Master Address: 3
4: Maximum Retry Count: 5
5: Retry Interval(sec): 5
<ESC>: Cancel menu level
Please select a key ?>