Designing a Liebert XD Solution
16
3.6.2 Determining Vertical Placement of Liebert XDOs Above the Cold Aisle
In the maximum density configuration, Emerson recommends placing the Liebert XDOs between 18 
and 24 inches (457-609mm) above the equipment cabinets. In some cases where the required density 
is less, the front-to-rear spacing of Liebert XDOs in a row will be increased. To ensure coverage of the 
wider spaces between the Liebert XDO units, the vertical distance between the cabinets and the Lie-
bert XDOs should be increased. However, the recommended maximum height of the Liebert XDO 
above the cabinets is 30 inches (762mm). See Figures 15.
Figure 15 Liebert XDO spacing—horizontal and vertical
Front-to-rear spacing of 
pairs of XDO modules
XDO height above
equipment to be cooled
Heat-Generating Critical Equipment
Pairs of XDO modules 
above critical equipment
Liebert recom-
mends install-
ing one Liebert 
XDO at the end 
of each aisle 
being cooled 
and to space 
the remainder 
between these 
“end units” in 
pairs. This lay-
out will block 
the incursion of 
hot air around 
the side of the 
end cabinets.