Designing a Liebert XD Solution
17
3.7
Liebert XDV Unit Placement
Liebert XDV units should be placed on top of the cabinets that generate the greatest amount of heat. 
If heat loads are dispersed evenly throughout the room, the Liebert XDV modules may be spread out 
accordingly.
The Liebert XDV must be placed toward the front of the equipment cabinet, so that its front bottom 
edge is flush with the front top edge of the cabinet. Placing the unit farther back on the top of the unit 
will restrict airflow into the cold aisle. Placing the unit farther to the front will decrease the amount 
of hot air drawn into the unit.
Figure 16 Positioning Liebert XDV on top of cabinet
Both of the Liebert XDV’s power cords should be connected to power sources. If only one power source 
is available, then only the power cord labeled “SECONDARY” should be connected to the power 
source.
Piping for the Liebert XDV is routed upward to the main return and supply pipes to and from the Lie-
bert XDP/Liebert XDC.
Table 4, below, may be used to determine the correct number of Liebert XDV modules.
Table 4
Determine required number of Liebert XDV modules (example below is Liebert XDV10)
Input Information
Step
Results
Total heat load in the room, kW
A
Reserve capacity needed
(10% to 25% of A is 
recommended)
B
C
Required cooling capacity, kW = A + B 
Existing/planned Liebert 
Deluxe/DS sensible capacity, kW
D
E
Required Liebert XD system cooling capacity, kW = C – D
F
Number of Liebert XDV10 modules required = E ÷ 10, rounded up (60Hz)
= E ÷ 8, rounded up (50Hz)
G
Number of Liebert XDP/Liebert XDC modules required = F ÷ 16, rounded 
up (60Hz and 50Hz)
Room area, square feet
H
I
Area served by each Liebert XDV10 = H ÷ F
L
Required Liebert XD system cooling density = E x 1000 ÷ H
OK if under 580 for 12-foot cold aisle spacing
OK if under 435 for 16-foot cold aisle spacing
Otherwise, additional Liebert Deluxe or Liebert DS unit capacity is 
needed.
INCORRECT
Liebert XDV 
hangs over front 
edge of rack
INCORRECT
Liebert XDV is 
too far from front
edge of rack
CORRECT
Liebert XDV is flush with
front edge of rack
X
Liebert XDV is suspended 
from ceiling structure...
X
...
.the separation 
between the rack and 
the Liebert XDV 
should be held to 
less than 1" (25mm). 
If this is not possible, 
an air blocker should 
be added to prevent 
unwanted airflow 
between the hot aisle 
and the cold aisle.