Raritan Computer EMX2-111 Manuel D’Utilisation

Page de 379
 
Chapter 10: Using the Command Line Interface 
 
 
315
 
 
Specifying the Rack Unit Numbering Offset 
This command syntax specifies the starting number of rack units on the 
asset sensors connected to the EMX device. 
config:# 
assetStrip <n> rackUnitNumberingOffset <number> 
 
Variables: 
 
<n> is the number of the FEATURE port where the selected asset 
sensor is physically connected. For the EMX device with only one 
FEATURE port, the number is always 1. 
 
<number> is a starting number for numbering rack units on the 
connected asset sensor. This value is an integer number. 
 
 
Example 
The following command specifies the starting number of rack units of the 
asset sensor #1 to be 5. That is, the rack units are numbered 5, 6, 7 and 
so on from the first to the final rack unit on the asset sensor #1. 
config:# 
assetStrip 1 rackUnitNumberingOffset 5 
 
 
Specifying the Asset Sensor Orientation 
This command syntax specifies the orientation of the asset sensors 
connected to the EMX device. Usually you do not need to perform this 
command unless your asset sensors do NOT come with the tilt sensor, 
causing the EMX unable to detect the asset sensors' orientation. 
config:# 
assetStrip <n> assetStripOrientation <orientation> 
 
Variables: 
 
<n> is the number of the FEATURE port where the selected asset 
sensor is physically connected. For the EMX device with only one 
FEATURE port, the number is always 1. 
 
<orientation> is one of the options: topConnector or 
bottomConnector
Orientation 
Description 
topConnector 
This option indicates that the asset sensor is 
mounted with the RJ-45 connector located on 
the top.