Mitsumi electronic NZ2GF-ETB Manuel D’Utilisation
121
CHAPTER 7 COMMUNICATION OF THE ETHERNET ADAPTER MODULE
7
7.3 IP C
ommunications over
CC-
Link IE F
ield Netw
ork (IP Packet
Tran
sfer
Function)
Function)
7.3.6 C
hecking communications (IP communication test)
7.3.6
Checking communications (IP communication test)
After the setting on Page 108, Section 7.3.3 to Page 118, Section 7.3.5 is completed, communications using the IP
address can be performed between the external devices.
Use the IP communication test of the configuration tool to check that communications can be performed. The following
items can be checked:
address can be performed between the external devices.
Use the IP communication test of the configuration tool to check that communications can be performed. The following
items can be checked:
• The cables on the communication route are properly connected.
• The parameter settings that are required for IP communications in an external device on the communication
• The parameter settings that are required for IP communications in an external device on the communication
route, such as the IP address, routing parameters on the master and local stations, and CC-Link IE Field
Network gateway setting on the Ethernet adapter module, are correct.
Network gateway setting on the Ethernet adapter module, are correct.
• Modules, such as a CPU module, master/local module, and Ethernet adapter module, that do not support
the IP packet transfer function are connected or not on the communication route.
(1) Test method
1.
Open the "IP Communication Test" dialog box in the configuration tool.
[Online]
[Diagnostics]
button
2.
Enter the IP address of the external device (request destination device) for "Communication
Target".
Target".
3.
Click the
button.