Mitsumi electronic NZ2GF-ETB Manuel D’Utilisation

Page de 246
123
CHAPTER 7 COMMUNICATION OF THE ETHERNET ADAPTER MODULE
7
7.3  IP C
ommunications over
 CC-
Link IE F
ield Netw
ork (IP Packet 
Tran
sfer
 Function)
7.3.6  C
hecking communications (IP communication test)
(2) Corrective action upon abnormal end
(a) If a network number, station number, and an error code are displayed
An error has occurred in the station with the network number and station number displayed. Check the error 
code and take corrective action.
(b) If the cause cannot be identified from symptoms such as a timeout error display
Enter the IP address in a module closest to the device where the IP communication test was executed. Repeat 
the test until the station that cannot receive communications is found.
In the following system configuration, execute the IP communication test in order of 
 to 
.
1
5
3
6
Master station
Station No.1
Station No.2
Network No.1
Network No.3
Source where the 
IP communication test 
was executed
Network No.2
Network No.1
6
192.168.3.1
192.168.2.1
192.168.3.30
192.168.2.30
192.168.1.1
192.168.1.125
192.168.1.2
Ethernet
CC-Link 
IE Field 
Network
IP address