 ION 7500 / ION 7600 User’s Guide
Page 24
Chapter 2 - Using The Front Panel 
Automatic Units
The front panel automatically scales the units for basic measurements, such as 
voltage, current and power parameters. For example, a measurement of 2,000 
Watts is displayed as 2.000 kW. A measurement of 2,000,000 Watts is displayed as 
2.000 MW. The meter makes these conversions using your PT and CT ratios.
The meter only performs these automatic units if the measurement is derived 
solely from the Power Meter module’s output.
Phasor Diagram Displays
Phase information can be displayed in phasor diagram format. Phasor diagrams 
are accompanied by tables that state the angle and magnitude of each phasor.
In cases where phasors are too small to be represented graphically, they are only 
shown as table entries.
Event Log Displays
Event Log displays alert you to recent events written to the meter’s event log. The 
vertical (Up/Down) navigation buttons are used to move through the list.
Details on altering the meter’s Event Log characteristics, such as log depth and 
logging frequency, using Designer can be found in the "Default Functionality" 
chapter.
Nameplate Displays
Like Event Log displays, Nameplate displays show information in tabular format. 
Default nameplates show owner, meter, and power system details.
See the section "Time-Of-Use Configuration" in the Default Meter Functionality 
chapter for details on configuring the T
AG
 strings.
Histogram Displays
Harmonics content is displayed in histogram format. Harmonics are displayed 
from the 2
nd
 to the 63
rd
 harmonic, with Total Harmonic Distortion (THD) values 
displayed above the histogram (K Factor and Crest Factor only appear in current 
harmonic histograms).
Use the vertical navigation buttons on the meter front panel to select individual 
harmonics (from 2
nd
 to 40
th
) in the histogram and view data specific to each of 
them (V
1
, V
2
, V
3
, I
1
, I
2
, and I
3
 only). 
An arrow
 appears below the harmonic selected. Harmonic magnitude is 
displayed as an absolute value and as a percentage of the fundamental. The phase 
angle of each harmonic is also provided. To return to the THD values, position the 
arrow below the fundamental.