Multi-Tech Systems 7600 Manuel D’Utilisation

Page de 372
ION 7500 / ION 7600 User’s Guide
Display Screen Types
Chapter 2 - Using The Front Panel 
Page 25
Trend Bar Graph Displays
Bar graph displays can show up to four real-time (numeric) parameters along with 
their upper and lower extremes.
Each bar graph automatically scales its output based on the magnitude of its 
extremes. The real-time value of each bar graph is displayed to the right of the 
graph. Note that scaling is applied separately to each bar graph in the display. Do 
not
 compare the magnitudes of two values based on the size of their bars.
In the trend bar graph shown on the left, the present value of Vll ab is 271.93 V. The 
bar graph also indicates that it has gone as low as 271.40 V and as high as 272.47 V.
Trend Displays
The Trend Display screen graphs the historical data of up to four different 
parameters simultaneously. A movable cursor that consists of the intersection of a 
vertical line and a horizontal line displays the value and timestamp of any plotted 
data within a parameter. The cursor displays the values of one parameter at one 
time only. With the Up and Down navigation keys, the cursor can move from one 
parameter to another.
In addition, a Trend Display log screen displays data logs for any graphed 
parameter – up to 3360 logs for each parameter. That is equivalent to 35 days worth 
of 15 minute data. The graph is updated when a new set of values is recorded. The 
highest supported update speed is once per second.
The ION 7500 front panel displays three preconfigured trending screens: V-Trend 
(voltage), I-Trend (current), and P-Trend (power). The ION 7600 must be 
configured using Designer in order to provide Trend Display. Contact Technical 
Services if you require your ION 7600 to be configured for Trend Display.