RAD Data comm IPmux-16 Manuel D’Utilisation

Page de 99
Chapter 3  Operation 
IPmux-16 Installation and Operation Manual 
3-40 Configuring IPmux-16
 
 
Table 3-3.  E1/T1 Alarms and Statistics 
Alarm Failure Comments 
LOS 
Loss of Signal 
Sync LED Off. 
• 
For T1: A second during which 192 contiguous pulse positions have no 
pulse of either positive or negative polarity (signal is more than 30 dB 
below nominal amplitude. 
• 
For E1: A second during which 255 contiguous pulse positions have no 
pulse of either positive or negative polarity. 
LOF 
Loss of Frame  Sync LED off. 
• 
For E1/T1: A second during which an OOF (see below) error persists for 
2.5 seconds and no AIS error (see below) is detected. 
LCV Line 
Code 
Violation 
• 
Line Code Violation 
For T1: A second during which BPV (Bipolar Violation) or EXZ errors have 
occurred. 
• 
For E1: A second during which two consecutive BPVs of the same 
polarity are received. 
• 
BPV is the occurrence of a pulse with the same polarity as the previous 
pulse. 
• 
EXZ is the occurrence of a zero string greater than 15 for AMI or 7 for 
B8ZS. 
• 
Complies with ITU-TI.431, 0.161, G.775 and G.821 standards. 
Rcv RAI 
(Yellow 
Alarm) 
Remote 
Alarm 
Indication 
The Sync LED flashes. 
• 
For E1/T1, a second during which an RAI pattern is received from the far 
end when the far-end framer enters a RED state (Loss of Frame). 
AIS Alarm 
Indication 
Signal–
Received 
from User 
The Sync LED is off. 
• 
For T1: A second during which an unframed “all 1” signal is received for 
3 milliseconds. 
• 
For E1: A second during which a string of 512 bits contains fewer than 
three zero (0) bits.