GFK-1004B
Table B-1.  Pinouts of the Serial Port
ÁÁÁÁÁ
ÁÁÁÁÁ
Pin Number
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
Signal
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Description
ÁÁÁÁÁ
ÁÁÁÁÁ
1
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
Shield
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Chassis Ground (optional)
ÁÁÁÁÁ
ÁÁÁÁÁ
2
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
TXD
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Transmit Data (output)
ÁÁÁÁÁ
ÁÁÁÁÁ
3
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
RXD
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Receive Data (input)
ÁÁÁÁÁ
ÁÁÁÁÁ
7
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
Common
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Signal Ground
ÁÁÁÁÁ
ÁÁÁÁÁ
(all others)
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Unused
Serial  Cable
A serial cable is needed to connect the GSM to the Ethernet Interface.  The next two
figures illustrate typical cable connection of a personal computer.   Figure B-1 shows
connections to a personal computer with a 25–pin serial port and Figure B-2 shows
connections to a personal computer with a 9-pin serial port..
RS-232 CABLE
* THE PINS AND CONNECTOR MAY BE DIFFERENT FOR
SOME COMPUTERS OR TERMINALS, BUT THE SIGNAL
NAMES WILL BE THE SAME. CONSULT THE MANUAL
FOR YOUR COMPUTER OR ASCII TERMINAL FOR THE
CORRECT SIZE CONNECTOR AND PIN NUMBERS.
3
2
*
PIN
*
25-PIN
MALE
25-PIN
SERIAL PORT
ON
PERSONAL
COMPUTER
25-PIN
FEMALE
2
3
a45181
PIN
9-PIN
MALE
ETHERNET
INTERFACE
MODULE
SERIAL
PORT
9-PIN
FEMALE
ÎÎ
ÎÎ
ÎÎ
ÎÎ
Î
Î
Î
ÎÎ
ÎÎ
Î
ÎÎ
ÎÎ
Î
ÎÎ
Î
Î
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
Î
Î
Î
ÎÎ
Î
ÎÎ
ÎÎ
ÎÎ
ÎÎ
Î
Î
ÎÎ
ÎÎ
Î
ÎÎ
Î
7
7
RXD
TXD
GND
TXD
RXD
GND
Figure B-1.    Serial Cable to Connect GSM (25–Pin Connector) to Ethernet Interface
 RS-232 CABLE
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
a45182
PIN
* 2
PIN
9-PIN
FEMALE
9-PIN
MALE
 ETHERNET
INTERFACE
MODULE
SERIAL
PORT
* THE PINS AND CONNECTOR MAY BE DIFFERENT FOR SOME COMPUTERS OR TERMINALS, BUT
THE SIGNAL NAMES WILL BE THE SAME. CONSULT THE MANUAL FOR YOUR COMPUTER OR ASCII
TERMINAL FOR THE CORRECT SIZE AND PIN NUMBERS.
9-PIN
MALE
9-PIN
SERIAL PORT
ON
PERSONAL
COMPUTER
9-PIN
FEMALE
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
2
3
7
TXD
RXD
GND
RXD
TXD
GND
* 3
* 5
 
Figure B-2.    Serial Cable to Connect GSM (9–Pin Connector) to Ethernet Interface
Display Terminal  Settings
When used as a local Station Manager terminal, set the terminal to “Wrap-Around”
mode.  This prevents loss of information in the event a Station Manager command
response exceeds the display line width of the terminal.