Emerson 610 Manuel D’Utilisation

Page de 112
Wiring Considerations
22
7.1
Power Wiring
1. Power wiring—rectifier input, bypass input, UPS output and battery cables—must be run in 
individual, separate conduits or cable trays. Refer to the Outline and Terminal Details drawings 
(Figures 14 through 3047495153 and 75 through 78) for locations of the various power 
connections within the UPS and ancillary equipment. In particular, note the location of the 
rectifier input power connections.
2. Observe local, state and national electrical codes. Verify utility power and its overcurrent 
protection rating will accommodate the UPS input rating, including battery recharging.
3. A safety ground wire must be run from the building ground to a ground point in the UPS Module 
Cabinets, ancillary equipment and the Power-Tie Cabinet (if applicable). See 6.0 - Configuring 
Your Neutral and Ground Connections. The grounding conductor shall comply with the 
following conditions of installation:
a. An insulated grounding conductor must be sized in accordance with the NEC and local codes. 
It must be green (with or without one or more yellow stripes) and be installed as part of the 
branch circuit that supplies the unit or system.
b. The grounding conductor described above is to be grounded to earth at the service equipment 
or, if supplied by a separately derived system, at the supply transformer or motor-generator 
set in accordance with the instructions in 6.0 - Configuring Your Neutral and Ground 
Connections.
c. The attachment-plug receptacles in the vicinity of the unit or system are all to be of a 
grounding type, and the grounding conductors serving these receptacles are to be connected to 
earth ground at the service equipment.
4. Observe clockwise phase rotation of all power wiring. Phase A leads Phase B leads Phase C.
A qualified electrician should check the phase rotation.
5. AC power cables must be rated to meet NEC requirements for voltage drop at the maximum rated 
system current. DC power cables from the UPS to the battery terminals and return must be sized 
for less than 2 volts total loop drop at the maximum rated system current.
6. If site equipment includes a backup generator and automatic transfer switch(es), consult the 
manufacturers of those devices for information on sizing and interfacing to the UPS system.
7. Removable access plates are available for power wiring. Refer to the Outline Drawings for your 
particular model (Figures 141618202224262847495153 and 75 through 78).
!
CAUTION 
Power and control wiring must be separated! 
!
CAUTION
After cutting holes in the access plates, be certain that no foreign matter (metal shavings, 
sawdust, insulation or wire fragments, etc.) remains inside the UPS. Likewise be certain to 
block any “extra” holes in the plates through which foreign matter could later enter the UPS.