Emerson BACNET IP Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
95
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Alarm Points
Discrete alarm objects available;
use auto-discover for this unit
Communications
—
40289
1
—
Bit 0
Output Undervoltage
—
40289
1
—
Bit 1
Output Overvoltage
—
40289
1
—
Bit 2
Output Overcurrent
—
40289
1
—
Bit 3
Frequency Deviation
—
40289
1
—
Bit 4
Ground Overcurrent
—
40289
1
—
Bit 5
Transformer Overtemp
—
40289
1
—
Bit 6
Ground Fault
—
40289
1
—
Bit 7
Ground Failure
—
40289
1
—
Bit 8
Liquid Detected
—
40289
1
—
Bit 9
Security Alarm
—
40289
1
—
Bit 10
Phase Rotation/Loss
—
40290
1
—
Bit 0
Datawave Overtemperature
—
40290
1
—
Bit 1
Emergency Shutdown
—
40290
1
—
Bit 2
Load On Bypass
—
40290
1
—
Bit 3
Local Alarm #1
—
40290
1
—
Bit 4
Local Alarm #2
—
40290
1
—
Bit 5
Output Voltage THD
—
40290
1
—
Bit 6
Custom Alarm #1
—
40290
1
—
Bit 7
Custom Alarm #2
—
40290
1
—
Bit 8
Setpoints (View)
None
None
—
—
1
—
—
Control Points (Set)
None
None
—
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 33
Liebert Datawave
™
, Liebert FPC
™
, Liebert PPC
™
- Input and Holding - PMP, PM2 Options for
Liebert FPC and Liebert PPC (continued)
Controller
Power Monitoring Panel - PMP, PM2 Options for Liebert FPC and Liebert PPC
Liebert Products
Liebert Datawave
Liebert FPC
Liebert PPC
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale Notes
/
Units