Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
95
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Alarm Points 
Discrete alarm objects available; 
use auto-discover for this unit
Communications
40289
1
Bit 0
Output Undervoltage
40289
1
Bit 1
Output Overvoltage
40289
1
Bit 2
Output Overcurrent
40289
1
Bit 3
Frequency Deviation
40289
1
Bit 4
Ground Overcurrent
40289
1
Bit 5
Transformer Overtemp
40289
1
Bit 6
Ground Fault
40289
1
Bit 7
Ground Failure
40289
1
Bit 8
Liquid Detected
40289
1
Bit 9
Security Alarm
40289
1
Bit 10
Phase Rotation/Loss
40290
1
Bit 0
Datawave Overtemperature
40290
1
Bit 1
Emergency Shutdown
40290
1
Bit 2
Load On Bypass
40290
1
Bit 3
Local Alarm #1
40290
1
Bit 4
Local Alarm #2
40290
1
Bit 5
Output Voltage THD
40290
1
Bit 6
Custom Alarm #1
40290
1
Bit 7
Custom Alarm #2
40290
1
Bit 8
Setpoints (View)
None
1
Control Points (Set)
None
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 33
Liebert Datawave
, Liebert FPC
, Liebert PPC
 - Input and Holding - PMP, PM2 Options for 
Liebert FPC and Liebert PPC (continued)
Controller
Power Monitoring Panel - PMP, PM2 Options for Liebert FPC and Liebert PPC
Liebert Products
Liebert Datawave
Liebert FPC
Liebert PPC
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale Notes 
Units