Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
96
Table 34
Liebert Datawave
, Liebert FPC
, Liebert PPC
 - Input and Holding - PMP Option for 
Liebert FPC and Liebert PPC
Controller
Power Monitoring Panel - PMP
Option for Liebert FPC and Liebert PPC
Liebert Products
Liebert Datawave
Liebert FPC
Liebert PPC
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale 
Notes / Units
Status Points (View)
Voltage In X-Y
40001
1
V
Voltage In Y-Z
40002
1
V
Voltage In Z-X
40003
1
V
Voltage Out A-B
40004
1
V
Voltage Out B-C
40005
1
V
Voltage Out C-A
40006
1
V
Voltage Out A-N
40007
1
V
Voltage Out B-N
40008
1
V
Voltage Out C-N
40009
1
V
Current Out A
40010
1
A
Current Out B
40011
1
A
Current Out C
40012
1
A
Ground Current
40013
1
10
A
Neutral Current
40014
1
A
kVA
40015
1
kVA
kW
40016
1
kW
Frequency
40017
1
10
Hz
% Capacity A
40018
1
%
% Capacity B
40019
1
%
% Capacity C
40020
1
%
Alarm Points 
Discrete alarm objects available; use auto-
discover for this unit
Communications
40289
1
Bit 0
Output Undervoltage
40289
1
Bit 1
Output Overvoltage
40289
1
Bit 2
Output Overcurrent
40289
1
Bit 3
Frequency Deviation
40289
1
Bit 4
Ground Overcurrent
40289
1
Bit 5
Transformer Overtemp
40289
1
Bit 6
Ground Fault
40289
1
Bit 7
Ground Failure
40289
1
Bit 8
Liquid Detected
40289
1
Bit 9
Security Alarm
40289
1
Bit 10
Phase Rotation/Loss
40290
1
Bit 0
Datawave Overtemperature
40290
1
Bit 1
Emergency Shutdown
40290
1
Bit 2
Load On Bypass
40290
1
Bit 3
Local Alarm
40290
1
Bit 4
Custom Alarm #1
40290
1
Bit 5
Custom Alarm #2
40290
1
Bit 6
Setpoints (View)
None
1
Control Points (Set)
None
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.