Emerson BACNET IP Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
100
Table 36
Liebert FDC
™
, Liebert FPC
™
, Liebert RDC
™
, Liebert RX
™
- Input and Holding
Controller
Liebert iCOM
®
v4
Liebert Products
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Input Power 1
Input Voltage A-B
Input Voltage A-B
30385
—
1
—
VAC
Input Voltage B-C
30386
—
1
—
VAC
Input Voltage C-A
30387
—
1
—
VAC
Input Power 2
Input Voltage A-B
Input Voltage A-B
30391
—
1
—
VAC
Input Voltage B-C
30392
—
1
—
VAC
Input Voltage C-A
30393
—
1
—
VAC
Output Power 1
—
—
Output Voltage X-Y
30397
—
1
—
VAC
Output Voltage Y-Z
30398
—
1
—
VAC
Output Voltage Z-X
30399
—
1
—
VAC
Output Voltage Vx
30400
—
1
—
VAC
Output Voltage Vy
30401
—
1
—
VAC
Output Voltage Vz
30402
—
1
—
VAC
Output Current Ix
30403
—
1
—
A AC
Output Current Iy
30404
—
1
—
A AC
Output Current Iz
30405
—
1
—
A AC
Output Neutral Current
30406
—
1
—
A AC
Ground Current
30407
—
1
10
A AC
Output Frequency
30408
—
1
—
Hz
Output Power (kVA)
30409
—
1
—
kVA
Output Power (kW)
30410
—
1
—
kW
Output kW-Hrs
30411
40411
2
—
kWH
Output Power Factor
30413
—
1
100
—
Output Percent Load
30414
—
1
—
%
Output Voltage Vx THD
30415
—
1
10
% THD
Output Voltage Vy THD
30416
—
1
10
% THD
Output Voltage Vz THD
30417
—
1
10
% THD
Output Current Ix THD
30418
—
1
10
% THD
Output Current Iy THD
30419
—
1
10
% THD
Output Current Iz THD
30420
—
1
10
% THD
Output Current Ix K-Factor
30421
—
1
10
—
Output Current Iy K-Factor
30422
—
1
10
—
Output Current Iz K-Factor
30423
—
1
10
—
Output Current Ix Crest Factor
30424
—
1
10
—
Output Current Iy Crest Factor
30425
—
1
10
—
Output Current Iz Crest Factor
30426
—
1
10
—