Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
102
Panel Main Current Ix
30471
1
A AC
Panel Main Current Iy
30472
1
A AC
Panel Main Current Iz
30473
1
A AC
Panel Main Neutral Current
30474
1
A AC
Panel Main Ground Current
30475
1
10
A AC
Panel Main Output Power (kVA)
30476
1
kVA
Panel Main Output Power (kW)
30477
1
kW
Panel Main Output kW-Hrs
30478
40478
2
10
kWH
Panel Main Output Power Factor
30480
1
100
Panel Main Output Percent Load
30481
1
%
Panel Main Voltage Vx THD
30482
1
10
% THD
Panel Main Voltage Vy THD
30483
1
10
% THD
Panel Main Voltage Vz THD
30484
1
10
% THD
Panel Main Current Ix THD
30485
1
10
% THD
Panel Main Current Iy THD
30486
1
10
% THD
Panel Main Current Iz THD
30487
1
10
% THD
Panel Main Current Ix Crest Factor
30488
1
10
Panel Main Current Iy Crest Factor
30489
1
10
Panel Main Current Iz Crest Factor
30490
1
10
Panel 2
Columns of Breakers
30494
1
Number of Breakers
30495
1
Panel Main Voltage X-Y
30496
1
VAC
Panel Main Voltage Y-Z
30497
1
VAC
Panel Main Voltage Z-X
30498
1
VAC
Panel Main Voltage X-N
30499
1
VAC
Panel Main Voltage Y-N
30500
1
VAC
Panel Main Voltage Z-N
30501
1
VAC
Panel Main Current Ix
30502
1
A AC
Panel Main Current Iy
30503
1
A AC
Panel Main Current Iz
30504
1
A AC
Panel Main Neutral Current
30505
1
A AC
Panel Main Ground Current
30506
1
10
A AC
Panel Main Output Power (kVA)
30507
1
kVA
Panel Main Output Power (kW)
30508
1
kW
Panel Main Output kW-Hrs
30509
40509
2
10
kWH
Panel Main Output Power Factor
30511
1
100
Panel Main Output Percent Load
30512
1
%
Panel Main Voltage Vx THD
30513
1
10
% THD
Table 36
Liebert FDC
, Liebert FPC
, Liebert RDC
, Liebert RX
 - Input and Holding (continued)
Controller
Liebert iCOM
®
 v4
Liebert Products
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg.
Scale 
Notes / Units