Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - UPS Systems
137
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 47
Liebert GXT2
 and Liebert GXT3
 - Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Input Lines
30004
40004
1
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
Bits 4 - 7
Number of Output Lines
30004
40004
1
Bits 8 - 11
Number of SubModules
30009
40009
1
Load Circuit Present
30013
40013
1
There are 16 possible Load 
Circuits. Each bit represents 1 
Load Circuit. Load Circuit 1 is bit 0, 
Load Circuit 2 is bit 1 and so on. If 
the bit is 1, then the Load Circuit is 
supported.
Battery Cabinet Type
30018
40018
2
Battery Cabinet Number
30019
40019
1
Battery AmpHour
30020
40020
1
AH
Nominal Power Rating
30021
40021
2
VA
Nominal Input Voltage
30027
40027
1
V
Nominal Output Voltage
30028
40028
1
V
Nominal Static Bypass Switch Voltage
30029
40029
1
V
Nominal Input Current
30030
40030
1
A
Nominal Input Frequency
30031
40031
1
10
Hz
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
Nominal Battery Voltage
30034
40034
1
V
Auto Restart Delay
30051
40051
1
Seconds
Device Low Battery Time
30053
40053
1
Minutes
Load (Apparent Power)
30102
2
VA
Load (Real Power)
30104
2
W
Load / Capacity
30106
1
%
Input Frequency
30107
1
10
Hz
Output Frequency
30108
1
10
Hz
Bypass Frequency
30109
1
10
Hz
Battery Charge Status
30112
1
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage
30113
1
V
Battery Time Remaining
30115
1
Minutes
Battery Charge Percentage
30116
1
%
Ambient Temperature
30119
1
deg C
Battery Test Result
30130
1
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited
Input Voltage L1
30153
1
V
Bypass Voltage L1
30159
1
V
Output Voltage L1
30163
1
V