Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
138
Output Current L1
30164
1
A
Input Maximum Voltage L1
30180
1
V
Input Minimum Voltage L1
30181
1
V
Output Maximum Voltage L1
30182
1
V
Output Minimum Voltage L1
30183
1
V
Black Out Count
30301
1
Brown Out Count
30302
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 48
Liebert HiNet
 - Status and Coil
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
DC-To-DC Converter On
10042
1
Load On Inverter
10073
1
Bypass Active
10074
1
Load On Battery
10128
1
Permanently On Bypass
10133
1
Bypass SCR Open Circuit
10149
1
Low Battery - Shutdown Imminent
10152
1
Output Overload
10154
1
Inverter Unsynchronized
10160
1
Input Power Supply Fail
10186
1
Bypass Input Voltage/Frequency Fault
10202
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 49
Liebert HiNet - Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Input Lines
30004
40004
1
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
Bits 4 - 7
Number of Output Lines
30004
40004
1
Bits 8 - 11
Number of SubModules
30009
40009
1
-
Number of Battery Cells
30012
40012
1
-
Load (Apparent Power)
30102
2
VA
Load (Real Power)
30104
2
W
Input Frequency
30107
1
10
Hz
Output Frequency
30108
1
10
Hz
Battery Voltage
30113
1
V
Battery Current (Charge/Discharge)
30114
1
A
Battery Charge Percentage
30116
1
%
Ambient Temperature
30119
1
deg C
Input Voltage L1
30153
1
V
Input Current L1
30154
1
A
Output Voltage L1
30163
1
V
Output Current L1
30164
1
A
Input Voltage L2
30203
1
V
Input Current L2
30204
1
A
Input Voltage L3
30253
1
V
Input Current L3
30254
1
A
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 47
Liebert GXT2
 and Liebert GXT3
 - Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units