Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
140
Table 51
Liebert Nfinity
®
 - Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale Notes 
Units
Number of Input Lines
30004
40004
1
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
Bits 4 - 7
Number of Output Lines
30004
40004
1
Bits 8 - 11
Number of Power Mod.
30010
40010
1
Number of Battery Modules Installed
30011
40011
1
Device Maximum Frame Capacity
30023
40023
2
Device System Capacity
30025
40025
2
VA
Nominal Input Voltage
30027
40027
1
V
Nominal Output Voltage
30028
40028
1
V
Nominal Static Bypass Switch Voltage
30029
40029
1
V
Nominal Input Frequency
30031
40031
1
10
Hz
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
Nominal Battery Voltage
30034
40034
1
V
Auto Restart Delay
30051
40051
1
Seconds
Device Auto Restart Percent Setpt
30052
40052
1
%
Device Low Battery Time
30053
40053
1
Minutes
Next Battery Auto Test Time
30057
40057
1
Minutes
Overload Alarm Limit
30067
40067
2
VA
Minimum Redundant Power Modules
30074
40074
1
Load (Apparent Power)
30102
2
VA
Load (Real Power)
30104
2
W
Load / Capacity
30106
1
%
Input Frequency
30107
1
10
Hz
Output Frequency
30108
1
10
Hz
Bypass Frequency
30109
1
10
Hz
Battery Charge Status
30112
1
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage
30113
1
V
Battery Time Remaining
30115
1
Minutes
Battery Charge Percentage
30116
1
%
Battery Temperature
30117
1
deg C
Transformer Temperature
30121
1
deg C
Redundant Power Modules
30124
1
Active Power Module Count
30126
1
Battery Module Active Count
30127
1
Battery Test Result
30130
1
-
Input Voltage L1
30153
1
V
Input Current L1
30154
1
A
Bypass Voltage L1
30159
1
V
Bypass Current L1
30160
1
A
Output Voltage L1
30163
1
V
Output Current L1
30164
1
A
Power Module Failure Count
30304
1
Battery Module Failure Count
30305
1
Power Module Warning Count
30306
1
Battery Module Warning Count
30307
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.