Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - UPS Systems
163
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 57
Liebert NXL
 - 60Hz, UL version (Model 40) - Glossary
Data Label
Data Description
Auto Restart In Progress 
Auto restart is in progress 
Auto Restart Inhibited - Ext 
Auto restart inhibited due to an external signal 
Auto Retransfer Time Remaining 
Time remaining before an inverter overload or inverter fault can be 
cleared and auto retransfer from the bypass to the inverter can take place 
Automatic Restart Failed 
Automatic restart failed 
Backfeed Breaker Open 
The backfeed breaker is in the open position 
Backfeed Breaker 
Backfeed breaker 
Battery - External Monitor 1 
External battery monitor 1 - battery maintenance required 
Battery - External Monitor 2 
External battery monitor 2 - battery maintenance required 
Battery Amp-Hours Consumed This Discharge 
Battery amp-hours withdrawn this discharge. 
Battery Amp-Hours Consumed 
Cumulative battery amp-hours withdrawn over the life of the battery 
Battery Capacity Low 
Battery capacity is low 
Battery Cell Count - Lead Acid 
Battery cell count - lead acid 
Battery Cell Count-Nickel Cadmium 
Battery cell count - nickel cadmium 
Battery Charging Inhibited 
Battery charging is inhibited due to an external inhibit signal 
Battery Charging Reduced-Extrnl 
Using a reduced battery charging algorithm due to an external signal 
Battery Circuit Breaker 1 Open 
Battery circuit breaker 1 is open 
Battery Circuit Breaker 2 Open 
Battery circuit breaker 2 is open 
Battery Circuit Breaker 3 Open 
Battery circuit breaker 3 is open 
Battery Circuit Breaker 4 Open 
Battery circuit breaker 4 is open 
Battery Circuit Breaker 5 Open 
Battery circuit breaker 5 is open 
Battery Circuit Breaker 6 Open 
Battery circuit breaker 6 is open 
Battery Circuit Breaker 7 Open 
Battery circuit breaker 7 is open 
Battery Circuit Breaker 8 Open 
Battery circuit breaker 8 is open 
Battery Commission Date 
Date and time when battery placed into service 
Battery Discharge Power 
Instantaneous battery power while discharging
Battery Discharge Time 
The time on battery operation for this discharge 
Battery Discharging 
The battery is discharging 
Battery Equalize 
The rectifier output voltage is increased to equalize the battery voltage 
level. 
Battery Ground Fault 
Battery system ground fault amperage exceeds the threshold 
Battery Last Discharge Date 
The date and time of the last battery discharge 
Battery Low Shutdown 
Battery disconnect due to end-of-discharge. 
Battery Low 
The calculated battery time remaining has reached the low battery 
threshold 
Battery Over Temperature 
A battery temperature sensor is reporting a value above a threshold 
Battery Percentage Charge 
The percentage of battery charge 
Battery Self Test 
Battery self test is in progress 
Battery Temperature for Cabinet 
The battery temperature for a cabinet 
Battery Temperature Imbalance 
Excessive temperature differences between battery sensors detected 
Battery Temperature Sensor Fault 
A battery temperature sensor fault has been detected 
Battery Test Failed 
Battery test failed 
Battery Test Inhibited 
Automatic (scheduled) battery tests are inhibited 
Battery Time Remaining 
The calculated available time on battery