Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
164
Battery Total Discharge Time 
The cumulative battery discharge time 
Battery Volts at Main Disconnect 
The voltage between the positive and the negative battery terminals of the 
common battery disconnect 
Battery Volts for Cabinet 
The voltage between the positive and negative battery terminals of a 
battery cabinet 
Bypass - Excess Auto Retransfers 
The number of auto retransfers, from bypass to inverter, has exceeded 
the maximum for a specified time interval 
Bypass - Manual Rexfr Inhibited 
Manual transfer from bypass to inverter is inhibited. 
Bypass - Manual Xfr Inhibited 
Manual transfer from inverter to bypass is inhibited. 
Bypass Auto Retransfer Failed 
After performing a recoverable transfer to bypass, an attempt to auto 
retransfer from bypass to inverter failed 
Bypass Auto Transfer Failed 
An automatic transfer to static bypass failed 
Bypass Excessive Pulse Parallel 
The system has performed too many pulse parallel operations within a 
specified time interval 
Bypass Frequency Error 
The bypass frequency is outside the inverter synchronization limits 
Bypass Input Frequency 
The bypass input frequency 
Bypass Input Voltage RMS A-B 
The bypass input RMS voltage between phases A and B 
Bypass Input Voltage RMS B-C 
The bypass input RMS voltage between phases B and C 
Bypass Input Voltage RMS C-A 
The bypass input RMS voltage between phases C and A 
Bypass Isolation Breaker (BIB) 
Bypass isolation breaker (BIB) 
Bypass Nominal Voltage 
Bypass nominal (or rated) voltage 
Bypass Not Available 
A problem associated with the bypass has been detected 
Bypass Overload Phase A 
An overload exists on output phase A while operating on the bypass 
Bypass Overload Phase B 
An overload exists on output phase B while operating on the bypass 
Bypass Overload Phase C 
An overload exists on output phase C while operating on the bypass 
Bypass Qualification Status 
bypass qualification status 
Bypass SS Overload Time Remain 
The calculated time remaining before bypass static switch shutdown due 
to the present overload condition
Bypass Static Switch Off Extrnl 
Bypass static switch is off due to the state of an external signal 
Bypass Static Switch Overload 
Bypass off due to static switch overload 
Bypass Static Switch Unavailable 
The static bypass switch is off, and unable to operate 
Bypass Sync Phase Difference 
The phase angle difference between the inverter output and bypass 
source 
Controls Reset Required 
A controls reset is required due to one or more critical settings changing 
DC Bus Current 
The current at the battery input terminals. In charging mode, the current 
will be a positive value. In discharging mode, the current will be a negative 
value 
DC Bus Ground Fault - Negative 
A ground fault has been detected on the negative DC Bus link 
DC Bus Ground Fault - Positive 
A ground fault has been detected on the positive DC Bus link 
DC Bus Qualification Status 
dc bus qualification status 
DC Bus Voltage 
The voltage between the positive and negative terminals of the DC bus at 
the battery input 
Equipment Over Temperature 
Equipment over temperature summary event 
Equipment Temperature Sensor Fail 
One or more temperature sensors report a temperature outside of the 
range of expected operation. 
Fuse Failure 
A summary event indicating one or more fuse failures 
Inlet Air Over Temperature 
The inlet air exceeds the maximum temperature threshold 
Table 57
Liebert NXL
 - 60Hz, UL version (Model 40) - Glossary (continued)
Data Label
Data Description