Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
168
Table 58
Liebert NXL
 - 50Hz, CE version (Models 48 and 49) - Status and Coil
Data Description
Status
Coil
Number
of Bits
Notes / Units
Input
System Input Power Problem
10001
1
Active on Alarm
System Input Phs Rotation Error
10002
1
Active on Alarm
System Input Current Limit
10003
1
Active on Alarm
System Input Current Imbalance
10004
1
Active on Alarm
Bypass
Bypass Not Available
10015
1
Active on Alarm
Bypass Overload Phase A
10016
1
Active on Alarm
Bypass Overload Phase B
10017
1
Active on Alarm
Bypass Overload Phase C
10018
1
Active on Alarm
Bypass Auto Retransfer Failed
10019
1
Active on Alarm
Bypass Static Switch Overload
10020
1
Active on Alarm
Bypass Static Switch Unavailable
10021
1
Active on Alarm
Bypass Auto Transfer Failed
10022
1
Active on Alarm
Bypass Frequency Error
10023
1
Active on Alarm
Bypass - Manual Rexfr Inhibited
10024
1
Active on Alarm
Bypass - Manual Xfr Inhibited
10025
1
Active on Alarm
Battery
Battery Automatic Test Inhibited
10036
1
Active on Alarm
Battery Capacity Low
10037
1
Active on Alarm
Battery Discharging
10038
1
Active on Alarm
Battery Temperature Imbalance
10039
1
Active on Alarm
Battery Equalize
10040
1
Active on Alarm
Battery Auto Test In Progress
10041
1
Active on Alarm
Main Battery Disconnect Open
10042
1
Active on Alarm
Battery Low
10043
1
Active on Alarm
Battery Temperature Sensor Fault
10044
1
Active on Alarm
Battery Circuit Breaker 1 Open
10045
1
Active on Alarm
Battery Circuit Breaker 2 Open
10046
1
Active on Alarm
Battery Circuit Breaker 3 Open
10047
1
Active on Alarm
Battery Circuit Breaker 4 Open
10048
1
Active on Alarm
Battery Circuit Breaker 5 Open
10049
1
Active on Alarm
Battery Circuit Breaker 6 Open
10050
1
Active on Alarm
Battery - External Monitor 1
10051
1
Active on Alarm
Battery - External Monitor 2
10052
1
Active on Alarm
Battery Ground Fault
10053
1
Active on Alarm
Battery Over Temperature Limit
10054
1
Active on Alarm
Battery Low Shutdown
10055
1
Active on Alarm
Battery Over Temperature
10056
1
Active on Alarm
Battery Test Failed
10057
1
Active on Alarm
Unexpected Main Battery Disconnect Closure
10058
1
Active on Alarm
Battery Over Voltage
10059
1
Active on Alarm
Battery Fuse Fault
10060
1
Active on Alarm
Main Battery Disconnect Forced To Unlock
10061
1
Active on Alarm
Battery Test Manually Stopped
10062
1
Active on Alarm
Battery Test Passed
10063
1
Active on Alarm
DC Bus