Emerson BACNET IP Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
170
UPS Output on Bypass
10177
—
1
Active on Alarm
Output Load on Maint. Bypass
10178
—
1
Active on Alarm
Backfeed Breaker Open
10179
—
1
Active on Alarm
Auto Restart In Progress
10180
—
1
Active on Alarm
Power Supply Failure
10181
—
1
Active on Alarm
Auto Restart Inhibited - Ext
10183
—
1
Active on Alarm
Automatic Restart Failed
10184
—
1
Active on Alarm
Main Controller Fault
10185
—
1
Active on Alarm
Fuse Failure
10186
—
1
Active on Alarm
System Controller Error
10187
—
1
Active on Alarm
System Breaker(s) Open Failure
10188
—
1
Active on Alarm
System Breaker(s) Close Failure
10189
—
1
Active on Alarm
Input Filter Cycle Lock
10190
—
1
Active on Alarm
EMO Shutdown
10191
—
1
Active on Alarm
Service Code Active
10192
—
1
Active on Alarm
LBS Active
10193
—
1
Active on Alarm
LBS Inhibited
10194
—
1
Active on Alarm
Regeneration Active
10195
—
1
Active on Alarm
Regeneration Operation Terminated
10196
—
1
Active on Alarm
Regeneration Operation Failure
10197
—
1
Active on Alarm
Leading Power Factor
10198
—
1
Active on Alarm
Controls Reset Required
10199
—
1
Active on Alarm
MultiModule
Loss of Redundancy
Loss of Redundancy
10212
—
1
Active on Alarm
MMS Overload
10215
—
1
Active on Alarm
MMS On Battery
10216
—
1
Active on Alarm
MMS Module Alarm Active
10218
—
1
Active on Alarm
Program Input Signals
Program Input Contact 01
Program Input Contact 01
10229
—
1
Active on Alarm
Program Input Contact 02
10230
—
1
Active on Alarm
Program Input Contact 03
10231
—
1
Active on Alarm
Program Input Contact 04
10232
—
1
Active on Alarm
Program Input Contact 05
10233
—
1
Active on Alarm
Program Input Contact 06
10234
—
1
Active on Alarm
Program Input Contact 07
10235
—
1
Active on Alarm
Program Input Contact 08
10236
—
1
Active on Alarm
Program Input Contact 09
10237
—
1
Active on Alarm
Program Input Contact 10
10238
—
1
Active on Alarm
Program Input Contact 11
10239
—
1
Active on Alarm
Program Input Contact 12
10240
—
1
Active on Alarm
Intelligent Paralleling
IP Inhibit
IP Inhibit
10251
—
1
Active on Alarm
ECO Mode
ECO Mode Active
ECO Mode Active
10262
—
1
Active on Alarm
ECO Mode Suspended
10263
—
1
Active on Alarm
Excess ECO Suspends
10264
—
1
Active on Alarm
Table 58
Liebert NXL
™
- 50Hz, CE version (Models 48 and 49) - Status and Coil
Data Description
Status
Coil
Number
of Bits
Notes / Units