Emerson BACNET IP Manuel D’Utilisation
![Emerson](https://files.manualsbrain.com/attachments/1ef3aaad462e024fde6cecf537a4c6c781334d44/common/fit/150/50/6dab323528eefa0342baa74a10c15551c3b956250cf9d62f2117dcdf42a7/brand_logo.jpeg)
Modbus 485 and Modbus IP Protocols - UPS Systems
181
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
EcoModeSchedule 14
Schedule Operation State - ECO Mode
31019
—
1
—
0 = disabled
1 = enabled
Schedule Action - ECO Mode
31020
—
1
—
0 = stop
1 = start
Schedule Day of Week - ECO Mode
31021
—
1
—
0 = Unknown
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
Schedule Hour - ECO Mode
31022
—
1
—
Units : hr
Uint16
Schedule Minute - ECO Mode
31023
—
1
—
Units : min
Uint16
Table 59
Liebert NXL™ - 50Hz, CE version (Models 48 and 49) - Input and Holding
Data Label
Input
Holding
# of Reg
Scale
Notes/Units