Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - UPS Systems
183
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Battery Time Remaining
The calculated available time on battery
Battery Total Discharge Time
The cumulative battery discharge time
Battery Volts at Main Disconnect
The voltage between the positive and the negative battery terminals of the common 
battery disconnect
Battery Volts for Cabinet
The voltage between the positive and negative battery terminals of a battery cabinet
Bypass - Manual Rexfr Inhibited
Manual transfer from bypass to inverter is inhibited.
Bypass - Manual Xfr Inhibited
Manual transfer from inverter to bypass is inhibited.
Bypass Auto Retransfer Failed
After performing a recoverable transfer to bypass, an attempt to auto retransfer from 
bypass to inverter failed
Bypass Auto Transfer Failed
An automatic transfer to static bypass failed
Bypass Frequency Error
The bypass frequency is outside the inverter synchronization limits
Bypass Input Frequency
The bypass input frequency
Bypass Input Voltage RMS A-B
The bypass input RMS voltage between phases A and B
Bypass Input Voltage RMS B-C
The bypass input RMS voltage between phases B and C
Bypass Input Voltage RMS C-A
The bypass input RMS voltage between phases C and A
Bypass Input Wire Configuration
Bypass input wire configuration
Bypass Isolation Breaker for Module 
1
Bypass isolation breaker for module 1
Bypass Isolation Breaker for Module 
2
Bypass isolation breaker for module 2
Bypass Isolation Breaker for Module 
3
Bypass isolation breaker for module 3
Bypass Isolation Breaker for Module 
4
Bypass isolation breaker for module 4
Bypass Isolation Breaker for Module 
5
Bypass isolation breaker for module 5
Bypass Isolation Breaker for Module 
6
Bypass isolation breaker for module 6
Bypass Isolation Breaker for Module 
7
Bypass isolation breaker for module 7
Bypass Isolation Breaker for Module 
8
Bypass isolation breaker for module 8
Bypass Isolation Breaker
Bypass isolation breaker
Bypass Nominal Voltage
Bypass nominal (or rated) voltage
Bypass Not Available
A problem associated with the bypass has been detected
Bypass Overload Phase A
An overload exists on output phase A while operating on the bypass
Bypass Overload Phase B
An overload exists on output phase B while operating on the bypass
Bypass Overload Phase C
An overload exists on output phase C while operating on the bypass
Bypass Qualification Status
bypass qualification status
Bypass SS Overload Time Remain
The calculated time remaining before bypass static switch shutdown due to the 
present overload condition
Bypass Static Switch Overload
Bypass off due to static switch overload
Bypass Static Switch Unavailable
The static bypass switch is off, and unable to operate
Bypass Sync Phase Difference
The phase angle difference between the inverter output and bypass source
Configuration Description
Configuration description
Continuous Operation - ECO Mode
This setting gives the user the ability to Enable/Disable ECO Mode continuous 
operation.
Table 60
Liebert NXL
 - 50Hz, CE version (Models 48 and 49) - Glossary
Data Label
Data Description