Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
188
Schedule Minute - ECO Mode
This setting represents the minute of the hour when an associated schedule entry 
action will take effect.
Schedule Operation State - ECO 
Mode
This setting gives the user the ability to either enable or disable a schedule entry if 
the action is Start.
Service Code Active
Service code is running
Static Bypass Switch
Static Bypass Switch state - On/Off
Static Switch Type
Static switch type configuration
Sum of MMS Output RMS Currents 
for Phase A
The sum of the multi-module system output RMS currents for phase A
Sum of MMS Output RMS Currents 
for Phase B
The sum of the multi-module system output RMS currents for phase B
Sum of MMS Output RMS Currents 
for Phase C
The sum of the multi-module system output RMS currents for phase C
System Breaker(s) Close Failure
One or more breakers in the system failed to close
System Breaker(s) Open Failure
One or more breakers in the system failed to open
System Controller Error
System controller internal error
System Date and Time
The system date and time
System Fan Capacity Status
System fan capacity status
System Fan Failure - Redundant
Redundant system fan failure
System Fan Redundant Status
System fan redundant status
System Fan Status
System fan status
System Input Current Imbalance
System Input Currents are Imbalanced
System Input Current Limit
The RMS input current has reached the input current limit threshold
System Input Frequency
The system input frequency
System Input Nominal Frequency
The nominal (or rated) system input frequency
System Input Nominal Voltage
The nominal (or rated) system input voltage
System Input Phs Rotation Error
The power conductors on the input line are not wired to the UPS in the sequence 
preferred for the rectifier (A-B-C)
System Input Power Problem
The input is not qualified to provide power to the system
System Input Power Source
System input power source
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
System Input RMS Current Phase C
The system input RMS current for Phase C
System Isolation Output Breaker
System isolation output breaker
System Load Bank Breaker
System load bank breaker
System Output Apparent Power
The sum total apparent power of all system output phases
System Output Breaker
System output breaker
System Output Fault
A fault has been detected in the system output
System Output Frequency
The system output frequency
System Output Low Power Factor
The system output power factor is low, resulting in reduced output capacity
System Output Maximum Amp 
Rating
System output maximum amperage rating
System Output Nominal Frequency
The nominal (or rated) system output frequency
Table 60
Liebert NXL
 - 50Hz, CE version (Models 48 and 49) - Glossary
Data Label
Data Description