Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
190
Table 61
Liebert PowerSure
 Interactive (before July 2008) - Status and Coil
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Audible Alarm Enabled
10002
2
1
Automatic Battery Test Enabled
10003
3
1
Battery Charge Compensation
10046
 —
1
Inverter Ready
10047
1
Load Circuit 1 State
10057
1
Load Circuit 2 State
10058
1
Load Circuit 3 State
10059
1
Load Circuit 4 State
10060
1
Load Circuit 5 State
10061
1
Load Circuit 6 State
10062
1
Load Circuit 7 State
10063
1
Load Circuit 8 State
10064
1
Load Circuit 9 State
10065
1
Load Circuit 10 State
10066
1
Load Circuit 11 State
10067
1
Load Circuit 12 State
10068
1
Load Circuit 13 State
10069
1
Load Circuit 14 State
10070
1
Load Circuit 15 State
10071
1
Load Circuit 16 State
10072
1
Load On Inverter
10073
1
Boost Mode On
10075
1
Buck Mode On
10076
1
Battery Under Test
10082
1
Shutdown Reason - Over Temperature
10086
1
Shutdown Reason - Overload
10087
1
Shutdown - Output Short
10089
1
Shutdown Reason - Remote Shutdown
10093
1
Load On Battery
10128
1
Output Off Pending
10151
1
Low Battery - Shutdown Imminent
10152
1
Output Overload
10154
1
Over Temperature Warning
10171
1
Battery Over Temperature CB Trip
10172
1
Input Power Supply Fail
10186
1
Input Over Voltage
10187
1
Input Under Voltage
10188
1
Bad Input Frequency
10190
1
Output Under Voltage
10218
1
Output Over Voltage
10219
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.