Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
202
Rectifier Block
40290
1
Bit 7
Rectifier Current Limit
40290
1
Bit 8
Rectifier Overtemperature
40290
1
Bit 9
Rectifier Fuse Failure
40290
1
Bit 10
Inverter Voltage Fault
40291
1
Bit 0
Inverter Disable
40291
1
Bit 1
Inverter Disable
40291
1
Bit 2
Inverter Current Limit
40291
1
Bit 3
Inverter Overtemperature
40291
1
Bit 4
Inverter Non Sync
40291
1
Bit 5
Inverter Overvoltage
40291
1
Bit 6
Inverter Undervoltage
40291
1
Bit 7
Inverter Fuse Failure
40291
1
Bit 8
Output Overvoltage
40291
1
Bit 9
Output Undervoltage
40291
1
Bit 10
Output Undervoltage
40292
1
Bit 0
Output Waveform Error
40292
1
Bit 1
Inverter Frequency Error
40292
1
Bit 2
Inverter Parallel Error
40292
1
Bit 3
Contactor Failure
40292
1
Bit 4
Battery Test
40292
1
Bit 5
Battery Test Failed
40292
1
Bit 6
Battery On Load
40292
1
Bit 7
Battery End of Discharge
40292
1
Bit 8
Boost Time Expired
40292
1
Bit 9
DC Overvoltage
40292
1
Bit 10
DC Undervoltage
40293
1
Bit 0
Battery Fuse Failure
40293
1
Bit 1
DC Overvoltage
40293
1
Bit 2
Transfer Count Block
40293
1
Bit 3
Overload Shutdown
40293
1
Bit 4
Overtemperature SD
40293
1
Bit 5
Emergency Stop
40293
1
Bit 6
Overload Present
40293
1
Bit 7
Overload Shutdown TO
40293
1
Bit 8
Display Error
40293
1
Bit 9
Display Error
40293
1
Bit 10
Inverter Over Capacity
40293
1
Bit 11
Bypass ECO Mode
40293
1
Bit 12
Fan Failure
40293
1
Bit 13
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 71
Liebert HiPulse
™,
 Liebert SICE 7200
- Input and Holding - SMM/SSM (continued)
Controller
Multi Module Series - SMM
Liebert Products
Liebert HiPulse
Liebert SICE 7200
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale Notes 
Units