Emerson BACNET IP Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
202
Rectifier Block
—
40290
1
—
Bit 7
Rectifier Current Limit
—
40290
1
—
Bit 8
Rectifier Overtemperature
—
40290
1
—
Bit 9
Rectifier Fuse Failure
—
40290
1
—
Bit 10
Inverter Voltage Fault
—
40291
1
—
Bit 0
Inverter Disable
—
40291
1
—
Bit 1
Inverter Disable
—
40291
1
—
Bit 2
Inverter Current Limit
—
40291
1
—
Bit 3
Inverter Overtemperature
—
40291
1
—
Bit 4
Inverter Non Sync
—
40291
1
—
Bit 5
Inverter Overvoltage
—
40291
1
—
Bit 6
Inverter Undervoltage
—
40291
1
—
Bit 7
Inverter Fuse Failure
—
40291
1
—
Bit 8
Output Overvoltage
—
40291
1
—
Bit 9
Output Undervoltage
—
40291
1
—
Bit 10
Output Undervoltage
—
40292
1
—
Bit 0
Output Waveform Error
—
40292
1
—
Bit 1
Inverter Frequency Error
—
40292
1
—
Bit 2
Inverter Parallel Error
—
40292
1
—
Bit 3
Contactor Failure
—
40292
1
—
Bit 4
Battery Test
—
40292
1
—
Bit 5
Battery Test Failed
—
40292
1
—
Bit 6
Battery On Load
—
40292
1
—
Bit 7
Battery End of Discharge
—
40292
1
—
Bit 8
Boost Time Expired
—
40292
1
—
Bit 9
DC Overvoltage
—
40292
1
—
Bit 10
DC Undervoltage
—
40293
1
—
Bit 0
Battery Fuse Failure
—
40293
1
—
Bit 1
DC Overvoltage
—
40293
1
—
Bit 2
Transfer Count Block
—
40293
1
—
Bit 3
Overload Shutdown
—
40293
1
—
Bit 4
Overtemperature SD
—
40293
1
—
Bit 5
Emergency Stop
—
40293
1
—
Bit 6
Overload Present
—
40293
1
—
Bit 7
Overload Shutdown TO
—
40293
1
—
Bit 8
Display Error
—
40293
1
—
Bit 9
Display Error
—
40293
1
—
Bit 10
Inverter Over Capacity
—
40293
1
—
Bit 11
Bypass ECO Mode
—
40293
1
—
Bit 12
Fan Failure
—
40293
1
—
Bit 13
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 71
Liebert HiPulse
™,
Liebert SICE 7200
™
- Input and Holding - SMM/SSM (continued)
Controller
Multi Module Series - SMM
Liebert Products
Liebert HiPulse
Liebert SICE 7200
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale Notes
/
Units