Modbus 485 and Modbus IP Protocols - UPS Systems
203
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 72
Liebert SICE 7200
 - Input and Holding - SSC
Controller
System Control Cabinet - SSC
Liebert Products
Liebert SICE 7200
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale Notes 
Units
Output Voltage L1-L2
40001
1
V
Output Voltage L2-L3
40002
1
V
Output Voltage L3-L1
40003
1
V
Output Amps L1
40004
1
A
Output Amps L2
40005
1
A
Output Amps L3
40006
1
A
Power L1
40007
1
kW
Power L2
40008
1
kW
Power L3
40009
1
kW
Bypass Frequency
40010
1
10
Hz
Battery Voltage
40012
1
V
Battery Amperage
40013
1
A
Apparent Power L1
40014
1
kVA
Apparent Power L2
40015
1
kVA
Apparent Power L3
40016
1
kVA
% Load L1
40017
1
%
% Load L2
40018
1
%
% Load L3
40019
1
%
% Battery Charge
40020
1
%
Battery Temperature
40021
1
deg C
Battery Time Remaining
40022
1
Minutes
Communications
40289
1
Bit 0
Bypass Switch Open
40289
1
Bit 1
Output Switch Open
40289
1
Bit 2
Battery CB Open
40289
1
Bit 3
Manual Bypass Closed
40289
1
Bit 4
Bypass Absent
40289
1
Bit 5
Bypass Overvoltage
40289
1
Bit 6
Bypass Undervoltage
40289
1
Bit 7
Bypass Frequency Error
40289
1
Bit 8
Bypass Ph Rotation Error
40289
1
Bit 9
Bypass SCR Failure
40289
1
Bit 10
Bypass Off
40290
1
Bit 0
Bypass Off
40290
1
Bit 1
Load On Bypass
40290
1
Bit 2
Bypass Overtemperature
40290
1
Bit 3
Inverter Non Sync
40290
1
Bit 4
Output Overvoltage
40290
1
Bit 5
Output Undervoltage
40290
1
Bit 6