Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
206
Equipment Over Temperature
40290
1
Bit 0
Any of Battery / Heatsink / Ambient / Timeout 
Shutdown
Battery Ground Fault CB Trip
40290
1
Bit 1
Power Supply Fail
40290
1
Bit 2
Any of Input / Bypass / Output / F1 / SWGR / 
MM / Option / AuEPO / LBS Power Fail
EPO Shutdown
40290
1
Bit 3
Rectifier Fail
40290
1
Bit 4
Inverter Fail
40290
1
Bit 5
Hardware Shutdown
40290
1
Bit 6
Battery Discharge
40290
1
Bit 7
Input Current Imbalance
40290
1
Bit 8
Input Line fail
40290
1
Bit 9
Input Under Voltage
40290
1
Bit 10
Input Over Voltage
40290
1
Bit 11
Input Over Current 
40290
1
Bit 12
Battery CB Open
40290
1
Bit 13
Battery Sync Error
40290
1
Bit 14
Bypass Voltage Out of Tolerance
40290
1
Bit 15
Bypass Line Fail
40291
1
Bit 0
Inverter Over Current
40291
1
Bit 1
Output OF/UF
40291
1
Bit 2
Inverter Overload
40291
1
Bit 3
Any of Inverter Phase A / B / C Overload
Excessive Auto Retransfer
40291
1
Bit 4
Equipment Over Temperature
Warning
40291
1
Bit 5
Any of AuBattery / Ambient / Heatsink / Inlet 
Over Temp Warning
Fan Fail
40291
1
Bit 6
Any of Power Pole Fan 1 / 2 / 3, Primary Fan 1 
/ 2 / 3 and System Fan Fail
SBS Unable
40291
1
Bit 7
Inverter Off By User
40291
1
Bit 8
Battery low Warning
40291
1
Bit 9
Battery Test Fail
40291
1
Bit 10
User Shutdown
40291
1
Bit 11
Load On Bypass
40291
1
Bit 12
Input Contact Alarms
40291
1
Bit 13
Any of Input Contact 1-8 Alarms
Generic Alarms
40291
1
Bit 14
Any other alarm conditions that are not 
mapped
Bypass Overload
40291
1
Bit 15
Any of Bypass A / B / C Overload
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 73
Liebert Npower
 - Input and Holding - IMP (continued)
Controller
Single Module Series - SMS
Liebert Products
Liebert Npower - SMS
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale 
Notes / Units