Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - UPS Systems
205
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 73
Liebert Npower
 - Input and Holding - IMP
Controller
Single Module Series - SMS
Liebert Products
Liebert Npower - SMS
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale 
Notes / Units
Status Points (View)
Input Voltage A-B
40001
1
V
Input Voltage B-C
40002
1
V
Input Voltage C-A
40003
1
V
Bypass Voltage A-B
40004
1
V
Bypass Voltage B-C
40005
1
V
Bypass Voltage C-A
40006
1
V
Battery Voltage
40007
1
V
Battery Current
40008
1
10
A
Battery Temperature
40009
1
deg C
Output Voltage A-B
40010
1
V
Output Voltage B-C
40011
1
V
Output Voltage C-A
40012
1
V
Output Current A
40013
1
10
A
Output Current B
40014
1
10
A
Output Current C
40015
1
10
A
Output kVA A
40016
1
kVA
Output kVA B
40017
1
kVA
Output kVA C
40018
1
kVA
Output kW A
40019
1
kW
Output kW B
40020
1
kW
Output kW C
40021
1
kW
Output Frequency
40022
1
10
Hz
Rated kVA Percentage
40023
1
%
Rated kW Percentage
40024
1
%
Alarm Points
Communications Loss
40289
1
Bit 0
Battery Fuse Fail
40289
1
Bit 1
Battery Low Transfer
40289
1
Bit 2
DC Over Voltage Transient
40289
1
Bit 3
Input Phase Rotation Error
40289
1
Bit 4
Rectifier/Trap Fuse Fail
40289
1
Bit 5
Any of Rectifier / Trap Fuse
Bypass Frequency Error
40289
1
Bit 6
Bypass Overload Shutdown
40289
1
Bit 7
Bypass Phase Rotation Error
40289
1
Bit 8
Inverter Over Voltage Transfer
40289
1
Bit 9
Inverter Fuse Fail
40289
1
Bit 10
Output Over Voltage Transfer
40289
1
Bit 11
Output Under Voltage Transfer
40289
1
Bit 12
SBS SCR Open
40289
1
Bit 13
SBS SCR Short
40289
1
Bit 14
Inverter Over Current Transfer
40289
1
Bit 15