Emerson BACNET IP Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
224
Supply Chilled Water Over Temp
Binary_Value
271
4626_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
Unit Code Missing
Binary_Value
272
5418_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
Unit Communication Lost
Binary_Value
273
5419_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
Water Leakage Detector Sensor Issue
Binary_Value
274
5114_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
Water Under Floor
Binary_Value
275
4723_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
Ext Over Temperature
Binary_Value
276
5104_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
External Fire Detected
Binary_Value
277
5108_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
Unspecified General Event
Binary_Value
278
5588_1
RD
Active on Alarm
2, 3, 4, 
5, 6
Temperature Control Sensor Issue
Binary_Value
279
5617_1
RD
Active on Alarm
2, 3, 4, 
5, 6
Airflow Sensor Issue
Binary_Value
280
5906_1
RD
Active on Alarm
5, 6
Ext Air Damper Position Issue
Binary_Value
281
5907_1
RD
Active on Alarm
5, 6
Ext Power Source A Failure
Binary_Value
282
5908_1
RD
Active on Alarm
5, 6
Ext Power Source B Failure
Binary_Value
283
5909_1
RD
Active on Alarm
5, 6
Mixed Mode Lockout
Binary_Value
284
5924_1
RD
Active on Alarm
5
System Events - Chilled Water Valve 1
Chilled Water Control Valve Failure
Binary_Value
288
4703_1_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
System Events - Chilled Water Valve 2
Chilled Water Control Valve Failure
Binary_Value
299
4703_1_2
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
System Events - Messages
Unit Off
Binary_Value
310
5110_1_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
Unit On
Binary_Value
311
5109_1_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
Unit Partial Shutdown
Binary_Value
312
5112_1_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
Unit Shutdown
Binary_Value
313
5113_1_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
Unit Standby
Binary_Value
314
5111_1_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
Maintenance Due
Binary_Value
315
5116_1_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
Maintenance Completed
Binary_Value
316
5117_1_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
System Events - Liebrt iCOM-DO Board 1
Digital Output Board Not Detected
Binary_Value
327
5417_1_1
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
System Events - iCOM DO Board 2
Digital Output Board Not Detected
Binary_Value
338
5417_1_2
RD
Active on Alarm
1, 2, 3, 
4, 5, 6
Table 76
Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
 - Binary Data (continued)
Controller
Liebert iCOM
®
 v4
Data Description
Object Type
Instance
Object
Name
Access
Notes
Extra
Notes