Emerson BACNET IP Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
226
Low Static Pressure
Binary_Value
565
5631_1
RD
Active on Alarm
3, 5, 6
Static Pressure Sensor Out of Range
Binary_Value
566
5910_1
RD
Active on Alarm
5, 6
EconoPhase
Pump Unspecified General Event
Binary_Value
623
5636_1
RD
Active on Alarm
4, 5
Global Condensers - GC Unit 1
Condenser Unit Unspecified General 
Event
Binary_Value
643
5637_1_1
RD
Active on Alarm
3, 4, 5, 6
Global Condensers - GC Circuit 1
Condenser Circuit Unspecified 
General Event
Binary_Value
644
5638_1_1
RD
Active on Alarm
3, 4, 5, 6
Power Measurement 1
Input Undervoltage
Binary_Value
1001
5568_1
RD
Active on Alarm
6
Power Measurement 2
Input Undervoltage
Binary_Value
1002
5568_2
RD
Active on Alarm
6
Power Measurement 6
Input Undervoltage
Binary_Value
1006
5568_6
RD
Active on Alarm
6
Fluid 1
Fluid Temperature Sensor Issue
Binary_Value
1021
5911_1
RD
Active on Alarm
6
Fluid Flow Sensor Issue
Binary_Value
1022
5912_1
RD
Active on Alarm
6
Fluid 2
Fluid Temperature Sensor Issue
Binary_Value
1031
5911_2
RD
Active on Alarm
6
Fluid Flow Sensor Issue
Binary_Value
1032
5912_2
RD
Active on Alarm
6
Table 77
Extra Notes to Table 76
Number
Description
1
This point is supported on:
iCOM controller version 1.04.042.STD
2
This point is supported on:
iCOM controller version 2.00.11R for US
iCOM controller version 2.00.12R (for Japan and China – language corrections only)
3
This point is supported on:
iCOM controller version 2.01.23R
4
This point is supported on:
iCOM controller version 2.02.16R
5
This point is supported on:
iCOM controller version 2.03.27.07R
6
This point is supported on:
iCOM controller version 2.01.32.02R
Table 76
Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
 - Binary Data (continued)
Controller
Liebert iCOM
®
 v4
Data Description
Object Type
Instance
Object
Name
Access
Notes
Extra
Notes