Emerson BACNET IP Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
235
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Fluid 1
Fluid Input Temperature
Analog_Value
871
5897_1
RD
Units: deg C
6
Fluid Input Temperature
Analog_Value
10871
5897_1_deg_F
RD
Units: deg F
6
Fluid Output Temperature
Analog_Value
872
5898_1
RD
Units: deg C
6
Fluid Output Temperature
Analog_Value
10872
5898_1_deg_F
RD
Units: deg F
6
Fluid 2
Fluid Input Temperature
Analog_Value
1871
5897_2
RD
Units: deg C
6
Fluid Input Temperature
Analog_Value
11871
5897_2_deg_F
RD
Units: deg F
6
Fluid Output Temperature
Analog_Value
1872
5898_2
RD
Units: deg C
6
Fluid Output Temperature
Analog_Value
11872
5898_2_deg_F
RD
Units: deg F
6
Circuit
Fluid Flow Rate
Analog_Value
881
5899_1
RD
Units: l/min
6
Circuit 2
Fluid Flow Rate
Analog_Value
891
5899_2
RD
Units: l/min
6
System Operations - Cooling Load 1
Circuit Cooling Load
Analog_Value
901
5905_1_1
RD
Units: kW
6
System Operations - Cooling Load 2
Circuit Cooling Load
Analog_Value
911
5905_1_2
RD
Units: kW
6
Table 79
Extra Notes to Table 78
Number
Description
1
This point is supported on:
iCOM controller version 1.04.042.STD
2
This point is supported on:
iCOM controller version 2.00.11R for US
iCOM controller version 2.00.12R (for Japan and China – language corrections only)
3
This point is supported on:
iCOM controller version 2.01.23R
4
This point is supported on:
iCOM controller version 2.02.16R
5
This point is supported on:
iCOM controller version 2.03.27.07R
6
This point is supported on:
iCOM controller version 2.01.32.02R
Table 78
Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
 - Analog Data (continued)
Data Label
Object Type
Instanc
e
Object  Name
Acces
s
Notes
Extra 
Notes