BACnet Communications - Thermal Management Products
237
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Fan Control Mode
MultiState_Value
82
5373_1
RW
1 = Auto
2 = Manual
3 = Economy
4 = Delta
1
Fan Control Sensor
MultiState_Value
83
5586_1
RW
1 = Supply
2 = Remote
3 = Return
4 = Manual
2, 3, 4, 
5, 6
System Info
System Status
MultiState_Value
93
4123_1
RD
1 = Normal 
Operation
2 = StartUp
3 = Normal with 
Warning
4 = Normal with 
Alarm
5 = Abnormal 
Operation
1, 2, 3, 
4, 5, 6
System Operating State
MultiState_Value
94
4706_1
RD
1 = off
2 = on
3 = standby
1, 2, 3, 
4, 5, 6
System Control Mode
MultiState_Value
95
4707_1
RD
1 = Internal (Auto)
2 = External 
(Manual)
1, 2, 3, 
4, 5, 6
System Operating State 
Reason
MultiState_Value
96
5074_1
RD
1 = Reason 
Unknown
2 = Network 
Display
3 = Alarm
4 = Schedule
5 = Remote 
System
6 = External Input
7 = Local Display
1, 2, 3, 
4, 5, 6
System Operations
Fan State
MultiState_Value
107
5381_1
RD
1 = off
2 = on
1, 2, 3, 
4, 5, 6
Cooling State
MultiState_Value
108
5382_1
RD
1 = off
2 = on
1, 2, 3, 
4, 5, 6
Free Cooling State
MultiState_Value
109
5383_1
RD
1 = off
2 = on
1, 2, 3, 
4, 5, 6
Maintenance Tracking State
MultiState_Value
110
5384_1
RD
1 = off
2 = on
1, 2, 3, 
4, 5, 6
Hot Water / Hot Gas State
MultiState_Value
111
5385_1
RD
1 = off
2 = on
1, 2, 3, 
4, 5, 6
Electric Reheat State
MultiState_Value
112
5386_1
RD
1 = off
2 = on
1, 2, 3, 
4, 5, 6
Dehumidifier State
MultiState_Value
113
5387_1
RD
1 = off
2 = on
1, 2, 3, 
4, 5, 6
Humidifier State
MultiState_Value
114
5388_1
RD
1 = off
2 = on
1, 2, 3, 
4, 5, 6
System On/Off Control
MultiState_Value
115
5143_1
RW
1 = off
2 = on
1, 2, 3, 
4, 5, 6
Table 80
Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
 - Multistate Data (continued)
Data Label
Object Type
Instance
Object Name
Access
Notes
Extra 
Notes