Emerson BACNET IP Manuel D’Utilisation
![Emerson](https://files.manualsbrain.com/attachments/1ef3aaad462e024fde6cecf537a4c6c781334d44/common/fit/150/50/6dab323528eefa0342baa74a10c15551c3b956250cf9d62f2117dcdf42a7/brand_logo.jpeg)
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
260
Remote Sensors 1
Remote Sensor Temperature
Remote Sensor Temperature
Analog_Value
56
5059_1
RD
Units: deg C
Remote Sensor Temperature
Analog_Value
10056
5059_1_deg_F
RD
Units: deg F
Remote Sensors 2
Remote Sensor Temperature
Remote Sensor Temperature
Analog_Value
67
5059_2
RD
Units: deg C
Remote Sensor Temperature
Analog_Value
10067
5059_2_deg_F
RD
Units: deg F
Remote Sensor Temperature
Analog_Value
155
5059_10
RD
Units: deg C
Remote Sensor Temperature
Analog_Value
10155
5059_10_deg_F
RD
Units: deg F
Chilled Water
Supply Chilled Water Temperature
Supply Chilled Water Temperature
Analog_Value
166
4624_1
RD
Units: deg C
Supply Chilled Water Temperature
Analog_Value
10166
4624_1_deg_F
RD
Units: deg F
Supply Chilled Water Over Temp Threshold
Analog_Value
167
4625_1
RW
Units: deg C
Supply Chilled Water Over Temp Threshold
Analog_Value
10167
4625_1_deg_F
RW
Units: deg F
System Info
BMS Timeout Period
BMS Timeout Period
Analog_Value
178
5075_1
RW
Units: min
Auto Restart Delay
Analog_Value
179
4710_1
RW
Units: sec
System Operations
Operating Efficiency
Operating Efficiency
Analog_Value
190
5076_1
RD
Units: %
Fan Speed
Analog_Value
191
5077_1
RD
Units: %
Cooling Capacity (Primary)
Analog_Value
192
5078_1
RD
Units: %
Dehumidifier Utilization
Analog_Value
193
5079_1
RD
Units: %
Reheat Utilization
Analog_Value
194
5080_1
RD
Units: %
Humidifier Utilization
Analog_Value
195
5081_1
RD
Units: %
Calculated Next Maintenance Month Analog_Value
196
4868_1
RD
—
Calculated Next Maintenance Year
Analog_Value
197
4869_1
RD
—
Maintenance Ramp
Analog_Value
198
4870_1
RD
Units: %
Time
System Date and Time
System Date and Time
Analog_Value
209
4293_1
RW
—
GlobalCondenser
Condenser Outside Air Temperature
Condenser Outside Air Temperature
Analog_Value
221
5534_1
RD
—
Condenser Outside Air Temperature
Analog_Value
10221
5534_1_deg_F
RD
—
GlobalCondenser - GC Fan 1
Condenser Fan Speed
Condenser Fan Speed
Analog_Value
233
5276_1_1
RD
Units: %
Condenser Fan Power
Analog_Value
234
5538_1_1
RD
Units: kW
GlobalCondenser - GC Fan 2
Condenser Fan Speed
Condenser Fan Speed
Analog_Value
246
5276_1_2
RD
Units: %
Condenser Fan Power
Analog_Value
247
5538_1_2
RD
Units: kW
GlobalCondenser - LowNoiseMode
Condenser Low Noise Mode Max Fan Speed
Condenser Low Noise Mode Max Fan Speed
Analog_Value
285
5548_1_1
RW
Units: %
Condenser Normal Mode Max Fan Speed
Analog_Value
286
5549_1_1
RW
Units: %
Table 84
Liebert CRV
™
- Analog Data (continued)
Controller Liebert iCOM
®
v4
Data Label
Object Type
Instance
Object
Name
Access
Notes