BACnet Communications - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
272
Fluid - Supply (Outlet) Fluid
Supply Fluid Over Temp
Binary_Value
84
4645_1_1
RD
Active on Alarm
1, 2
Supply Fluid Under Temp
Binary_Value
85
4648_1_1
RD
Active on Alarm
1, 2
Supply Fluid Temp Sensor Issue
Binary_Value
86
4651_1_1
RD
Active on Alarm
1, 2
Pumps
All Pumps Loss of Flow
Binary_Value
97
5297_1
RD
Active on Alarm
1, 2
Pump 1 Loss of Flow
Binary_Value
98
4656_1
RD
Active on Alarm
1, 2
Pump 2 Loss of Flow
Binary_Value
99
4659_1
RD
Active on Alarm
1, 2
Pumps - Pump 1
Pump Hours Exceeded
Binary_Value
110
5300_1_1
RD
Active on Alarm
1, 2
Pumps - Pump 2
Pump Hours Exceeded
Binary_Value
121
5300_1_2
RD
Active on Alarm
1, 2
Free Cooling
Free Cooling Valve Hours Exceeded
Binary_Value
132
5306_1
RD
Active on Alarm
1, 2
Ambient Air Temperature Sensor Issue
Binary_Value
133
4618_1
RD
Active on Alarm
1, 2
Evaporators
Evaporator Inlet Temp Sensor Issue
Binary_Value
144
5308_1
RD
Active on Alarm
1, 2
Evaporator Return Fluid Over Temp
Binary_Value
145
5559_1
RD
Active on Alarm
1, 2
Evaporator Return Fluid Under Temp
Binary_Value
146
5560_1
RD
Active on Alarm
1, 2
Evaporators - Evaporator 1
Evaporator Fluid Freeze - Auto Reset
Binary_Value
157
5310_1_1
RD
Active on Alarm
1, 2
Evaporator Fluid Freeze - Manual Reset 
Required
Binary_Value
158
5311_1_1
RD
Active on Alarm
1, 2
Supply Refrigerant Temp Sensor Issue
Binary_Value
159
4640_1_1
RD
Active on Alarm
1, 2
Evaporators - Evaporator 2
Evaporator Fluid Freeze - Auto Reset
Binary_Value
170
5310_1_2
RD
Active on Alarm
1, 2
Evaporator Fluid Freeze - Manual Reset 
Required
Binary_Value
171
5311_1_2
RD
Active on Alarm
1, 2
Supply Refrigerant Temp Sensor Issue
Binary_Value
172
4640_1_2
RD
Active on Alarm
1, 2
System Events
Customer Input 1
Binary_Value
183
4270_1
RD
Active on Alarm
1, 2
Customer Input 2
Binary_Value
184
4271_1
RD
Active on Alarm
1, 2
Customer Input 3
Binary_Value
194
4272_1
RD
Active on Alarm
2
Customer Input 4
Binary_Value
195
4273_1
RD
Active on Alarm
2
Unit On
Binary_Value
185
5109_1
RD
Active on Alarm
1, 2
Unit Off
Binary_Value
186
5110_1
RD
Active on Alarm
1, 2
Master Unit Communication Lost
Binary_Value
187
5120_1
RD
Active on Alarm
1, 2
Subgroup Event Occurred During 
Communication Loss
Binary_Value
188
5315_1
RD
Active on Alarm
1, 2
Humidifier Control Board Not Detected
Binary_Value
189
5045_1
RD
Active on Alarm
1, 2
RAM Battery Issue
Binary_Value
190
5119_1
RD
Active on Alarm
1, 2
Unit Code Missing
Binary_Value
191
5418_1
RD
Active on Alarm
1, 2
Unspecified General Event
Binary_Value
192
5588_1
RD
Active on Alarm
2
Unit Shutdown Unspecified General Event
Binary_Value
193
5775_1
RD
Active on Alarm
2
EEV 1
EEV Unspecified General Event
Binary_Value
200
5625_1
RD
Active on Alarm
2
Table 87
Liebert HPC
 - Binary Data (continued)
Controller Liebert iCOM
®
 v4
Data Label
Object Type
Instance
Object
Name
Access
Notes
Extra
Notes