Emerson BACNET IP Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
274
Free Cooling
Free Cooling External Temperature Delta
Analog_Value
112
5301_1
RW
Units: deg C
1, 2
Free Cooling External Temperature Delta
Analog_Value
10112
5301_1_deg_F
RW
Units: deg F
1, 2
Free Cooling Valve Open Position
Analog_Value
113
5303_1
RD
Units: %
1, 2
Free Cooling Valve Hours
Analog_Value
114
5304_1
RW
Units: hr
1, 2
Free Cooling Valve Hours Threshold
Analog_Value
115
5305_1
RW
Units: hr
1, 2
Evaporators
Evaporator Return Fluid Temperature
Analog_Value
126
5307_1
RD
Units: deg C
1, 2
Evaporator Return Fluid Temperature
Analog_Value
10126
5307_1_deg_F
RD
Units: deg F
1, 2
Evaporator Return Fluid Over Temp Alarm 
Threshold
Analog_Value
127
5555_1
RW
Units: deg C
1, 2
Evaporator Return Fluid Over Temp Alarm 
Threshold
Analog_Value
10127
5555_1_deg_F
RW
Units: deg F
1, 2
Evaporator Return Fluid Over Temp Warning 
Threshold
Analog_Value
128
5556_1
RW
Units: deg C
1, 2
Evaporator Return Fluid Over Temp Warning 
Threshold
Analog_Value
10128
5556_1_deg_F
RW
Units: deg F
1, 2
Evaporator Return Fluid Under Temp 
Warning Threshold
Analog_Value
129
5557_1
RW
Units: deg C
1, 2
Evaporator Return Fluid Under Temp 
Warning Threshold
Analog_Value
10129
5557_1_deg_F
RW
Units: deg F
1, 2
Evaporator Return Fluid Under Temp Alarm 
Threshold
Analog_Value
130
5558_1
RW
Units: deg C
1, 2
Evaporator Return Fluid Under Temp Alarm 
Threshold
Analog_Value
10130
5558_1_deg_F
RW
Units: deg F
1, 2
Brine
Supply Brine Temp Set Point
Analog_Value
141
5312_1
RW
Units: deg C
1, 2
Supply Brine Temp Set Point
Analog_Value
10141
5312_1_deg_F
RW
Units: deg F
1, 2
Standby Units
Standby Units
Analog_Value
152
5314_1
RW
1, 2
System Operations
Return Fluid Temperature
Analog_Value
163
5288_1
RD
Units: deg C
1, 2
Return Fluid Temperature
Analog_Value
10163
5288_1_deg_F
RD
Units: deg F
1, 2
Supply Fluid Temperature
Analog_Value
164
4643_1
RD
Units: deg C
1, 2
Supply Fluid Temperature
Analog_Value
10164
4643_1_deg_F
RD
Units: deg F
1, 2
Actual Supply Fluid Temp Set Point
Analog_Value
165
5282_1
RD
Units: deg C
1, 2
Actual Supply Fluid Temp Set Point
Analog_Value
10165
5282_1_deg_F
RD
Units: deg F
1, 2
Condenser Inlet Water Temperature
Analog_Value
166
5517_1
RD
Units: deg C
1, 2
Condenser Inlet Water Temperature
Analog_Value
10166
5517_1_deg_F
RD
Units: deg F
1, 2
Condenser Outlet Water Temperature
Analog_Value
167
5518_1
RD
Units: deg C
1, 2
Condenser Outlet Water Temperature
Analog_Value
10167
5518_1_deg_F
RD
Units: deg F
1, 2
Supply Heated Water Temp Set Point
Analog_Value
168
5313_1
RW
Units: deg C
1, 2
Supply Heated Water Temp Set Point
Analog_Value
10168
5313_1_deg_F
RW
Units: deg F
1, 2
Free Cooling Utilization
Analog_Value
169
5519_1
RD
Units: %
1, 2
Reheat Utilization
Analog_Value
170
5080_1
RD
Units: %
1, 2
Compressor Utilization
Analog_Value
171
5078_1
RD
Units: %
1, 2
Ambient Air Temperature
Analog_Value
172
4594_1
RD
Units: deg C
1, 2
Ambient Air Temperature
Analog_Value
10172
4594_1_deg_F
RD
Units: deg F
1, 2
Compressor Economizer Utilization
Analog_Value
173
5520_1
RD
Units: %
1, 2
Condenser Adiabatic Cooling Utilization
Analog_Value
174
5521_1
RD
Units: %
1, 2
Time
System Date and Time
Analog_Value
185
4293_1
RW
1, 2
Table 88
Liebert HPC
 - Analog Data (continued)
Controller Liebert iCOM
®
 v4
Data Label
Object Type
Instance
Object
Name
Access
Notes
Extra
Notes