BACnet Communications - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
276
Table 90
Extra Notes
Number
Description
1
This point is supported on: FDM v32
iCOM Controller Version 2.02.xxx
2
This point is supported on: FDM v101
iCOM Controller Version 2.03.xxx
Table 91
Liebert HPC
 - Glossary
Data Label
Data Description
Actual Supply Fluid Temp Set Point
The actual set point value being used for the desired fluid temperature at the outlet 
of the unit.
All Pumps Loss of Flow
System is shut down due to loss of flow in all available pumps.
Ambient Air Temperature Sensor Issue
The ambient air temperature sensor is disconnected or the signal is out of range.
Ambient Air Temperature
Ambient air temperature.
Compressor Capacity Control State
Compressor capacity control state. When 'ON', the cooling capacity of the 
compressor has been reduced.
Compressor Capacity Normal
Compressor has returned to normal load capacity.
Compressor Capacity Reduced
Compressor capacity has been reduced.
Compressor Contactor Issue
Compressor contactor is not closing during compressor startup or is not opening 
during compressor shutdown.
Compressor Economizer Utilization
Present compressor economizer utilization expressed as a percentage of the 
maximum.
Compressor Head Pressure
Compressor head pressure.
Compressor High Head Pressure
Compressor is shut down due to high head pressure.
Compressor Hours Exceeded
[Compressor Hours] has exceeded [Compressor Hours Threshold].
Compressor Hours Threshold
Threshold value used in the [Compressor Hours Exceeded] event.
Compressor Hours
Operating hours for compressor since last reset of this value.
Compressor Loss of Differential 
Pressure
Compressor is shut down due to low differential pressure.
Compressor Low Oil Pressure
Compressor low oil pressure.
Compressor Low Suction Pressure
Compressor is shut down due to low suction pressure.
Compressor Not Stopping
Compressor commanded to stop, but continues to run.
Compressor Shut Down - Ambient Air 
Low Temp Limit
When the temperature of ambient air falls below this lower threshold, the 
compressor will be shut off. Correct condensing pressure cannot be achieved 
when temperature is too low.
Compressor State
Compressor operational state.
Compressor Superheat Over 
Threshold
Compressor discharge refrigerant superheat temperature has exceeded an upper 
threshold.
Compressor Thermal Overload
Compressor is shut down due to thermal overload.
Compressor Utilization
Present compressor utilization expressed as a percentage of the maximum rated 
capacity.
Condenser Adiabatic Cooling 
Utilization
Present adiabatic cooling utilization expressed as a percentage of the maximum.
Condenser Fan Issue
Condenser fan is not operating within its operational parameters.
Condenser Fan Speed
Condenser fan speed expressed as a percentage of the maximum rated speed.
Condenser Inlet Water Temperature
For water cooled condensers, the temperature of the water entering the heat 
exchanger, before cooling the refrigerant.
Condenser Max Fan Speed Override
Fan speed exceeding the maximum set point in order to alleviate a high 
temperature or pressure condition.
Condenser Outlet Water Temperature
For water cooled condensers, the temperature of the water exiting the heat 
exchanger, after cooling the refrigerant.