Emerson BACNET IP Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
295
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Supply Fluid Over Temp Threshold
Threshold value used in the [Supply Fluid Over Temp] event.
Supply Fluid Over Temp
[Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp 
Threshold].
Supply Fluid Temp Sensor Issue - Event 
Control
Enable/disable the activation of the [Supply Fluid Temp Sensor Issue] event. If 
set to 'disabled', the event will not be annunciated. This implies that the event 
will not be placed in any active event list or in any event history list.
Supply Fluid Temp Sensor Issue - Event 
Type
The event type for the [Supply Fluid Temp Sensor Issue] event.
Supply Fluid Temp Sensor Issue
The supply fluid temperature sensor is disconnected or the signal is out of 
range.
Supply Fluid Temperature
Supply fluid temperature.
Supply Fluid Under Temp - Event Control
Enable/disable the activation of the [Supply Fluid Under Temp] event. If set to 
'disabled', the event will not be annunciated. This implies that the event will not 
be placed in any active event list or in any event history list.
Supply Fluid Under Temp - Event Type
The event type for the [Supply Fluid Under Temp] event.
Supply Fluid Under Temp
[Supply Fluid Temperature] has dropped below a specified threshold.
Supply Refrig Over Temp - Event Control
Enable/disable the activation of the [Supply Refrigerant Over Temp] event. If 
set to 'disabled', the event will not be annunciated. This implies that the event 
will not be placed in any active event list or in any event history list.
Supply Refrig Over Temp - Event Type
The event type for the [Supply Refrigerant Over Temp] event.
Supply Refrig Over Temp Threshold
Threshold value used in the [Supply Refrigerant Over Temp] event.
Supply Refrig Temp Sensor Issue - Event 
Control
Enable/disable the activation of the [Supply Refrigerant Temp Sensor Issue] 
event. If set to 'disabled', the event will not be annunciated. This implies that 
the event will not be placed in any active event list or in any event history list.
Supply Refrig Temp Sensor Issue - Event 
Type
The event type for the [Supply Refrigerant Temp Sensor Issue] event.
Supply Refrig Under Temp Control - Event
Enable/disable the activation of the [Supply Refrigerant Under Temp] event. If 
set to 'disabled', the event will not be annunciated. This implies that the event 
will not be placed in any active event list or in any event history list.
Supply Refrig Under Temp - Event Type
The event type for the [Supply Refrigerant Under Temp] event.
Supply Refrigerant Over Temp
Event that is activated when [Supply Refrigerant Temperature] exceeds 
[Supply Refrig Over Temp Threshold]. The event is deactivated when the 
temperature drops below the threshold.
Supply Refrigerant Temp Sensor Issue
The supply refrigeramt temperature sensor is disconnected or the signal is out 
of range.
Supply Refrigerant Temperature
Supply refrigerant temperature.
Supply Refrigerant Under Temp
[Supply Refrigerant Temperature] has dropped below a specified threshold.
System Condensation Detected - Event 
Control
Enable/disable the activation of the [System Condensation Detected] event. If 
set to 'disabled', the event will not be annunciated. This implies that the event 
will not be placed in any active event list or in any event history list.
System Condensation Detected - Event 
Type
The event type for the [System Condensation Detected] event.
System Condensation Detected
System condensation detected.
System Control Mode
System control mode.
System Date and Time
The system date and time
System Event Acknowledge/Reset
Reset and/or acknowledge all events.
System On/Off Control
Turn system functionality on or off.
System Operating State Reason
The reason the system is in the current operating state.
System Operating State
Current operating state of the system.
System Status
The operating status for the system.
Table 95
Liebert XDP
, Liebert XDC
 - Glossary (continued)
Data Label
Data Description