Emerson BACNET IP Manuel D’Utilisation
BACnet Communications - Thermal Management Products
297
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 96
Liebert DataMate
™
, Liebert Mini-Mate2
™
- MM2
Controller
MM2
Liebert Products
Liebert DataMate
Liebert Mini-Mate2
Data Description
BACnet Instance
Notes
Status Points (View)
Temperature
Temperature
BS01_x
—
Humidity
BS02_x
—
Cooling
BS03_x
1=On / 0=Off
Heating
BS04_x
1=On / 0=Off
Humidification
BS05_x
1=On / 0=Off
Dehumidification
BS06_x
1=On / 0=Off
Econ-o-Cycle
BS07_x
1=On / 0=Off
Stages
BS08_x
—
% Capacity
BS09_x
—
Unit On/Off
BS18_x
1=On / 0=Off
Alarm Points
Communications
Communications
BA01_x:00
—
Local Off
BA01_x:01
—
Remote Off
BA01_x:02
—
High Head Pressure 1
BA01_x:03
—
Loss of Airflow
BA01_x:05
—
Standby Glycol Unit On
BA01_x:06
—
Change Filters
BA01_x:07
—
High Temperature
BA01_x:08
—
Low Temperature
BA01_x:09
—
High Humidity
BA02_x:00
—
Low Humidity
BA02_x:01
—
Humidifier Problem
BA02_x:02
—
Smoke Detected
BA02_x:08
—
Loss of Water Flow
BA02_x:09
—
Standby Unit On
BA02_x:10
—
Short Cycle
BA03:01
—
Loss of Power
BA03:02
—
Local Alarm 1
BA03:06
—
Local Alarm 2
BA03:07
—
High Water
BA03:08
—
Local Alarm 4
BA03:09
—
Setpoints (View)
Temperature
Temperature
BS10_x
—
Humidity
BS12_x
—
Control Points (Set)
Remote On/Off
Remote On/Off
BC01_x
Bit 0 On=unit Off; Bit 1 On=unit On
Temperature Setpoint
BC02_x
—
Humidity Setpoint
BC03_x
—