Emerson BACNET IP Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
140
Table 51
Liebert Nfinity
®
- Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale Notes
/
Units
Number of Input Lines
30004
40004
1
—
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
—
Bits 4 - 7
Number of Output Lines
30004
40004
1
—
Bits 8 - 11
Number of Power Mod.
30010
40010
1
—
—
Number of Battery Modules Installed
30011
40011
1
—
—
Device Maximum Frame Capacity
30023
40023
2
—
—
Device System Capacity
30025
40025
2
—
VA
Nominal Input Voltage
30027
40027
1
—
V
Nominal Output Voltage
30028
40028
1
—
V
Nominal Static Bypass Switch Voltage
30029
40029
1
—
V
Nominal Input Frequency
30031
40031
1
10
Hz
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
—
Nominal Battery Voltage
30034
40034
1
—
V
Auto Restart Delay
30051
40051
1
—
Seconds
Device Auto Restart Percent Setpt
30052
40052
1
—
%
Device Low Battery Time
30053
40053
1
—
Minutes
Next Battery Auto Test Time
30057
40057
1
—
Minutes
Overload Alarm Limit
30067
40067
2
—
VA
Minimum Redundant Power Modules
30074
40074
1
—
—
Load (Apparent Power)
30102
—
2
—
VA
Load (Real Power)
30104
—
2
—
W
Load / Capacity
30106
—
1
—
%
Input Frequency
30107
—
1
10
Hz
Output Frequency
30108
—
1
10
Hz
Bypass Frequency
30109
—
1
10
Hz
Battery Charge Status
30112
—
1
—
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage
30113
—
1
—
V
Battery Time Remaining
30115
—
1
—
Minutes
Battery Charge Percentage
30116
—
1
—
%
Battery Temperature
30117
—
1
—
deg C
Transformer Temperature
30121
—
1
—
deg C
Redundant Power Modules
30124
—
1
—
—
Active Power Module Count
30126
—
1
—
—
Battery Module Active Count
30127
—
1
—
—
Battery Test Result
30130
—
1
—
-
Input Voltage L1
30153
—
1
—
V
Input Current L1
30154
—
1
—
A
Bypass Voltage L1
30159
—
1
—
V
Bypass Current L1
30160
—
1
—
A
Output Voltage L1
30163
—
1
—
V
Output Current L1
30164
—
1
—
A
Power Module Failure Count
30304
—
1
—
—
Battery Module Failure Count
30305
—
1
—
—
Power Module Warning Count
30306
—
1
—
—
Battery Module Warning Count
30307
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.