Emerson GXT2U Manuel D’Utilisation

Page de 40
30
Battery Cabinet Specifications
Model Number
GXT2-72VBATT
Used w/ UPS Model GXT2-2700RT208
DIMENSIONS in (mm)
Unit - W x D x H in. (mm) 3.5 x 24.2 x 17 (87 x 618 x 430)
Shipping - W x D x H in. (mm) 10.5 x 27.2 x 23 (268 x 692 x 585)
WEIGHT, lb (kg)
Unit: lbs (kg) 93.6 (42.5)
Shipping: lbs (kg) 102.5 (46.5)
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid
Qty x V x Rating 2 x 6 x 12V x 9.0 AH
Battery Mfg/Part # Panasonic/UP-VW1245P1
Yuasa/REW 45-12
ENVIRONMENTAL
Operating Temp +32°F to +104°F (0°C to +40°C)
Storage Temp +5°F to +122°F (-15°C to +50°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000 m) at 104°F (40°C) 
without derating
Storage Elevation 50,000 ft. (15,000 m) maximum
AGENCY
Safety UL 1778, c-UL Listed
RFI/EMI FCC Part 15, Subpart B, Class A
Transportation ISTA Procedure 1A