Emerson GXT2U Manuel D’Utilisation

Page de 40
31
Battery Run Times
Load %
Estimated Time
Internal Battery
(minutes)
10%
91
20%
46
30%
30
40%
21
50%
16
60%
11
70%
9
80%
8
90%
7
100%
5
Internal Battery 
+ 1 External Battery 
Cabinet (minutes)
10%
364
20%
184
30%
120
40%
84
50%
64
60%
44
70%
36
80%
32
90%
28
100%
20
Internal Battery 
+ 2 External Battery 
Cabinets (minutes)
10%
728
20%
368
30%
240
40%
168
50%
128
60%
88
70%
72
80%
64
90%
56
100%
40
Internal Battery 
+ 3 External Battery 
Cabinets (minutes)
10%
1092
20%
552
30%
360
40%
252
50%
192
60%
132
70%
108
80%
96
90%
84
100%
60