Chapter 3  Electrical Installation      25 
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA    User Manual 
A amplified view
A
Side cabinet
Main cabinet
Nut M10
Spring w asher 10
Plain w asher 10
Plain w asher 10
Bolt M10 *35
W6( red)
W5( green)
W4( yellow )
 
Figure 3-10    Power cable connection between main cabinet and side cabinet of 400kVA UPS (6-pulse rectifier) 
A
Main cabinet
A amplified view
Side cabinet
Nut M10
Spring w asher 10
Plain w asher 10
Bolt M10 *35
W6( red)
W5( green)
W4( yellow )
 
Figure 3-11    Power cable connection between main cabinet and side cabinet of 400kVA UPS (12-pulse rectifier) 
3.4.2   Connecting Signal Cables 
You need not connect signal cables between the main cabinet and side cabinet of the 300kVA UPS (12-pulse 
rectifier).  
When you connect signal cables between the main cabinet and side cabinet of the 400kVA UPS, you should connect 
the signal cables from the main cabinet to the corresponding ports on the ULW366SA8 board of the side cabinet. The 
connection relationship is shown in Table 3-9, you just need to connect the J2, J4, J6, J7 and J10 ports. The positions 
of the ports on the ULW366SA8 board are shown in Figure 3-12. 
Table 3-9    Signal cable connection between main cabinet and side cabinet of 400kVA UPS 
Port (side cabinet) 
Cable No. (main cabinet) 
Meaning 
J2 W98-12 
Fan 
power 
J4 W98-13 
Fan 
power 
J6 
W45 
Rectifier current detection 
J7 
W41-5 
Fuse fault detection 
J10 W58 
Rectifier 
drive