Emerson U/300/S/6P Manuel D’Utilisation

Page de 79
Chapter 4  Operator Control And Display Panel      27 
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA    User Manual 
Chapter 4   Operator Control And Display Panel 
This chapter expounds the functions and use of the components on the operator control and display panel of the 
HIPULSE U UPS, and provides LCD display information, including the LCD screen types, detailed menu messages, 
prompt windows and UPS alarm message list 
4.1   Introduction 
The operator control and display panel is located on the front door of the UPS. The panel is the access point for 
operator control and monitoring of all measured parameters, UPS and battery status and of event and alarm logs.   
The operator control and display panel is divided into three functional areas: mimic power flow chart, graphic LCD 
monitor with menu keys, control buttons, as shown in Figure 4-1. 
INVERTER
ON
FAULT
CLEAR
F2
F4
HELP
F1
F3
INVERTER
OFF
SILENCE
ON/OFF
12:30:36
Unit #1
Normal
?
Bypass
Main
Vphase V
Iphase   A
Freq. Hz
Vline V
P. F.
A(AB)
220
20.5
50.1
380
0.99
B(BC)
220
20.5
50.1
380
0.99
C(CA)
220
20.5
50.1
380
0.99
Output
Input Breaker Closed
10-12  12:28:16
Manual Turn On
10-12  12:30:06
UPS in Normal Mode
10-22  12:30:16
200kVA-3X3
HIPULSE U
2006-01-01
Mimic power flow chart
Control buttons
Battery LED
Buzzer
Graphic LCD monitor
with menu keys
Rectifier LED
Bypass LED
Inverter LED
Load LED
Alarm LED
LCD menu keys
 
Figure 4-1    Operator control and display panel 
4.1.1   LED Indicators   
The six LEDs mounted on the mimic flow chart represent the various power paths of the UPS, and indicate the 
current UPS operational status and alarm status by color (red, green, yellow) and state (ON, OFF, flashing), as 
described in Table 4-1. 
Table 4-1    Description of LED indicators 
LED 
State 
Description 
Steady green 
Rectifier in normal operation 
Flashing green 
Input AC normal, but rectifier not operating 
Steady red 
Rectifier f failed 
Rectifier LED 
OFF 
Rectifier not operating, input ac not available or out of normal range 
Steady green 
Load on bypass power 
Steady red 
Bypass not available, out of normal range or static bypass switch fault 
Bypass LED 
OFF 
Bypass normal, load not on bypass power 
Steady green 
Battery normal, but discharging and powering the load 
Flashing green 
Battery end-of-discharge pre-warning 
Steady red 
Battery abnormal (failed, absent or polarity reversed) or battery circuit breaker abnormal 
Battery LED 
OFF 
Battery and battery circuit breaker normal, battery charging 
Steady green 
Inverter normal and powering the load 
Flashing green 
Inverter ON, starting up, synchronizing, or standing by (ECO mode) 
Steady red 
Inverter failed 
Inverter LED 
OFF 
Inverter not operating