Emerson SERIES 600T Manuel D’Utilisation

Page de 168
UPS Interconnection Kits
96
Appendix A.5 Installing the Liebert FS With a Liebert HiPulse UPS
The Liebert HiPulse UPS interconnection kit for the Liebert FS is compatible with the Liebert 
HiPulse™ models in Table 28.
Appendix A.5.1 Description—HiPulse UPS Interconnection Kit
HiPulse UPS interconnection kit is composed of:
DC Power Interface
One Thermal-Magnetic Molded Case circuit-breaker rated for 250 ADC, 600VDC equipped with 
auxiliary contacts: two (2) sets of Normally Open (NO) and Normally Closed (NC).
Status/Control Interface
One Status/Control Terminal Block used to ensure the status/control connections between the 
Liebert FS and the Liebert HiPulse.
Appendix A.5.2 Status/Control Connections—Liebert HiPulse UPS Interconnection Kit
The status/control interface of the IKIT-A05 is the Status/Control Terminal Block. The connection of 
the Status/Control Terminal Block is illustrated in Figure 102. Please refer to this drawing to ensure 
that the proper connections are made. In case multiple Liebert FS units are connected to the same 
UPS DC bus, please refer to Figure 144 to perform the Status/Control connections between each 
Liebert FS.
This IKIT includes Status/Control Connections that enable transfer of “IKIT circuit-breaker status 
(closed/open)” signals between the Liebert FS system(s) and the UPS system.
Figure 102 Liebert HiPulse status/control terminal block wiring
The recommended gauge for Status/Control Connection wires is 16 AWG – 600 VDC (approximate 
metric equivalent: 1.3 mm² wire section). All wiring must comply with all applicable local, regional, 
national regulations.
Table 28
Liebert HiPulse model ratings
UPS Output Rating
kVA
80
120
160
200
300
400
500
600
800
kW
64
96
128
160
240
320
400
480
640
4
2
3
5
7
8
9
6
1
10
Two rows
B
l
u
e
B
l
u
e
Y
e
l
l
o
w
Y
e
l
l
o
w
Yellow/
Blue
Yellow/
Blue
Row for
installation of 
contractor wire 
connections