UPS Interconnection Kits
98
Appendix A.5.5 Single Liebert FS on UPS DC Bus
The following Liebert FS Software Control Parameters must be set when a single Liebert FS is con-
nected alone on the DC bus of the Liebert HiPulse UPS system.
Instructions on setting these parameters on the Liebert FS are found in 6.5.3 - Control Parameters 
Appendix A.5.6 Single Liebert FS in Parallel with Battery Pack on UPS DC Bus
The following Software Control Parameters must be reset when the Liebert FS is connected in paral-
lel with a battery pack on the DC bus of the Liebert Hipulse UPS system.
Instructions on setting these parameters on the Liebert FS are found in 6.5.3 - Control Parameters 
NOTE
The Software Control Parameter values specified below must be used unless otherwise 
specified by the Liebert-certified service technician at Initial System Startup.
Table 29
 Liebert FS Software Control Parameter settings
Liebert FS Software Control Parameter
Setting
Charge Voltage 
436 VDC
Regulation Voltage 
426 VDC
Vreg Delta
0 VDC
Maximum Charge Current
See Table 30
Charge Amps/Volts 
See Table 30
Table 30
Liebert FS Software Control Parameters varying with UPS size
UPS Output Rating (kVA)
80
120
Liebert FS 
Maximum Charge Current (A)
39
50
Liebert FS
 Charge Amps/Volts (A/V)
4
5
NOTE
The Software Control Parameter values specified below must be used unless otherwise 
specified by the Liebert-certified service technician at Initial System Startup. These values may 
require adjustments due to the battery type.
Table 31
Liebert FS Software Control Parameter settings
Liebert FS Software Control Parameter
Setting
Charge Voltage 
436 VDC
Regulation Voltage 
426 VDC
Vreg Delta
0 VDC
Maximum Charge Current
See Table 32
Charge Amps/Volts 
See Table 32
Table 32
Liebert FS Software Control Parameters varying with UPS size
UPS Output Rating (kVA)
80
120
Liebert FS Maximum Charge Current (A)
39
50
Liebert FS Charge Amps/Volts (A/V)
4
5